Télécharger Imprimer la page

Danfoss EKC 202D1 Mode D'emploi page 5

Masquer les pouces Voir aussi pour EKC 202D1:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Parameters
Function
Normal operation
Temperature (set point)
Thermostat
Differential
Max. limitation of setpoint setting
Min. limitation of setpoint setting
Adjustment of temperature indication
Temperature unit (°C/°F)
Correction of the signal from S4
Correction of the signal from S3
Manual service, stop regulation, start regulation
(-1, 0, 1)
Displacement of reference during night operation
Definition and weighting, if applicable, of thermo-
stat sensors - S4% (100%=S4, 0%=S3)
Activation of reference displacement r40
Value of reference displacement (activate via r39
or DI)
Thermostat sensor S4% can be selected under night
operation with night time cover.
Temperature difference for night time cover (0 K =
not detected)
Alarm
Delay for temperature alarm
Delay for door alarm
Delay for temperature alarm after defrost
High alarm limit
Low alarm limit
Alarm delay DI1
Alarm delay DI2
Definition of alarm sensor
1: Combination of S3 and S4 (A36, A13 and A14
must be set)
2: Separate values for S3 and S4 (A13, A14, A56 and
A57 must be set)
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
High alarm limit for S3
Low alarm limit for S3
Compressor
Min. ON-time
Min. OFF-time
Compressor relay 1 must cutin and out inversely
(NC-function)
Defrost
Defrost method (none/EL/GAS/BRINE)
Defrost stop temperature
Interval between defrost starts
Max. defrost duration
Displacement of time on cutin of defrost at start-up
Drip off time
Delay for fan start after defrost
Fan start temperature
Fan cutin during defrost
0: Stopped. 1: Running
2: Running during pump down and defrost
Defrost sensor (0=time, 1=S5, 2=S4)
Pump down delay
Max. aggregate refrigeration time between two
defrosts
Defrost on demand - S5 temperature's permitted
variation during frost build-up. On central plant
choose 20 K (=off )
Minimum defrost time
Fan
Fan stop at cutout compressor
Delay of fan stop
Fan stop temperature (S5)
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
Six start times for defrost.
Setting of minutes.
0=OFF
Clock - Setting of hours
Clock - Setting of minute
Clock - Setting of date
Clock - Setting of month
Clock - Setting of year
EKC 202D1
EL-diagram
number (page
1)
Codes 1
2
3
---
***
r01
***
r02
***
r03
r04
r05
r09
r10
r12
r13
r15
r39
r40
r61
r75
A03
***
A04
A12
***
A13
***
A14
A27
A28
A33
A36
A56
A57
c01
c02
c30
d01
d02
d03
d04
d05
d06
d07
d08
d09
d10
d16
d18
d19
d24
F01
F02
F04
t01-
t06
t11-
t16
***
t07
***
t08
***
t45
***
t46
***
t47
Instructions RI8NK459 © Danfoss 06/2015
English
Min.-
Max.-
Factory
Actual
value
value
setting
setting
-50.0°C
50.0°C
2.0°C
0.0 K
20.0K
2.0 K
-49.0°C
50°C
50.0°C
-50.0°C
49.0°C
-50.0°C
-20.0 K
20.0 K
0.0 K
°C
°F
°C
-10.0 K
+10.0 K
0.0 K
-10.0 K
+10.0 K
0.0 K
-1
1
0
-10.0 K
10.0 K
0.0 K
0%
100%
100%
OFF
ON
OFF
-50.0 K
50.0 K
0.0 K
0%
100%
100%
0 K
20 K
0 K
0 min
240 min 30 min
0 min
240 min 60 min
0 min
240 min 90 min
-50.0°C
50.0°C
8.0°C
-50.0°C
50.0°C
-30.0°C
0 min
240 min 30 min
0 min
240 min 30 min
1
2
1
0%
100%
100%
-50.0°C
50.0°C
8.0°C
-50.0°C
50.0°C
-30.0°C
0 min
30 min
0 min
0 min
30 min
0 min
0
1
0
OFF
ON
OFF
no
bri
EL
0.0°C
25.0°C
6.0°C
0 hours 240 hours 8 hours
0 min
180 min 45 min
0 min
240 min
0 min
0 min
60 min
0 min
0 min
60 min
0 min
-50.0°C
0.0°C
-50.0°C
0
2
1
0
2
0
0 min
60 min
0 min
0 hours
48 hours 0 hours
0.0 K
20.0 k
20.0 K
0 min
180 min
0 min
no
yes
no
0 min
30 min
0 min
-50.0°C
50.0°C
50.0°C
0 hours
23 hours 0 hours
0 min
59 min
0 min
0 hours
23 hours 0 hours
0 min
59 min
0 min
1
31
1
1
12
1
0
99
0
SW = 1.5x
Setting:
1 Open parameter r12 and stop the
regulation
2 Select electric connection based on
the drawings on page 1
3 Open parameter o61 and set the elec-
tric connection number in it
4 Now select one of the preset settings
from the table
5 Open parameter o62 and set the
number for the array of presettings.
The few selected settings will now be
transferred to the menu.
6 Regulation is now started (r12 was set
to 1 in point 5)
7 Go through the survey of factory set-
tings. Make any necessary changes in
the respective parameters.
8 For network. Set the address in o03
and then transmit it to the gateway/
system unit with setting o04.
5

Publicité

loading