Setting the measuring range (input range)
The measuring range setting defines the DC 0...10 V output sig-
nal (Analog Out).
LGni
LG-Ni1000
1
0.0...50.0
°C
2
-30.0...50.0
°C
3
-30.0...90.0
°C
4
-30.0...130.0
°C
5
-50.0...70.0
°C
6
-50.0...180.0
°C
7
32.0...122.0
F
8
-22.0...122.0
F
9
-22.0...194.0
F
10
-22...266
F
11
-58.0...158.0
F
12
-58...356
F
Pt A
Pt100
1
0.0...60.0
°C
2
-50.0...80.0
°C
3
-30.0...130.0
°C
4
32.0...140.0
F
5
-58.0...176.0
F
6
-22...266
F
dC
0-10 VDC
1
0.0...50.0
°C
2
0.0...70.0
°C
3
0.0...100.0
°C
4
0.0...130.0
°C
5
-10.0...120.0
°C
6
-35.0...35.0
°C
7
-50.0...50.0
°C
8
32.0...122.0
F
9
32.0...158.0
F
10
32...212
F
11
32...266
F
12
14...248
F
13
-31.0...95.0
F
14
-58.0...122.0
F
15
0.0...100.0
%
16
0.0...95.0
%
17
0.0...90.0
%
18
0...1999
ppm
19
0.0...10.0
V
2
20
0...1000
W/m
21
0.0...5.0
m / s
22
0.0...10.0
m / s
23
0.0...15.0
m / s
24
-50...50
Pa
25
0...100
Pa
Readjusting the display
corr
The measured value displayed can be matched to environmental
conditions
-3 ... 3
Software version
Press briefly
to display the software version.
4/12
22.12.2006
rAnG
t1
T1
1
-50.0...80.0
°C
2
-30.0...130.0
°C
3
-58.0...176.0
F
4
-22...266
F
Pt b
Pt1000
1
-50.0...80.0
°C
2
-30.0...130.0
°C
3
-20...400
°C
4
-58.0...176.0
F
5
-22...266
F
6
-4...752
F
26
0...200
Pa
27
0...250
Pa
28
0...300
Pa
29
0...500
Pa
30
0...1000
Pa
31
0...1500
Pa
32
20...300
Pa
33
50...500
Pa
34
100...1000
Pa
35
0.0...25.0
mbar
36
0.0...30.0
mbar
37
0...100
mbar
38
0...200
mbar
39
0...500
mbar
40
0...1000
mbar
41
0.00...2.00
bar
4
0.00...4.00
bar
43
0.00...5.00
bar
44
0.0...10.0
bar
45
0.0...16.0
bar
46
0.0...20.0
bar
47
0.0...25.0
bar
48
0.0...40.0
bar
49
-1.0...9.0
bar
50
-1.0...24.0
bar
G5312X
74 319 0565 0 a
Dimensions