If used in an EMERGENCY CIRCUIT, the enclosed "EMERGENCY CIRCUITS" label
shall be placed on the front of door to identify as a component of the emergency
system. If any Emergency Circuits are fed or controlled from this panel, it must be
located electrically where fed from a UPS, generator, or other guaranteed source of
power during emergency and power outage situations.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed
including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
a)
b) Do not use outdoors.
c) Do not mount near gas or electric heaters.
d) Equipment should be mounted in locations and at heights where it will not readily
be subjected to tampering by authorized personnel.
e) The use of accessory equipment not recommended by manufacturer may cause
an unsafe condition.
f) Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS
All servicing shall be performed by qualified service personnel.
WARNINGS AND CAUTIONS
•
TO AVOID FIRE, SHOCK OR DEATH: TURN OFF POWER at main circuit breaker, or fuse,
and test that the power is off before wiring, opening the panel, replacing any component
servicing the relay cabinet or fixture or when changing lamps.
•
DO NOT CONNECT line voltage wires to low voltage terminals.
•
To avoid electrical overload, total external connected load should not exceed output rating.
•
To be installed and/or used in accordance with appropriate electrical codes and regulations.
•
To be installed by an electrician.
•
Conduit Entry Locations: The cabinets have been designed with specific locations
supporting conduit entry for line and low voltage circuits. There are specific areas of the
cabinet which are restricted from some or all types of conduit access. Reference the
Physical Installation section of this manual for specific details.
•
Line & Load Circuit Wiring: The line wiring should come from an over-current device and
the load circuit wiring shall go to the specific load to be controlled. On some models which
have integrated branch circuit protection, the line side of the relay has been pre-wired to a
circuit breaker. With these products, only the load side of the circuits needs to be connected.
•
Mount in a location where audible noise is acceptable.
•
When using with fluorescent ballasts, both lighting fixture and ballast must be grounded.
•
Use this relay cabinet only with minimum 75
•
For indoor use only.
•
During operation, cabinet cover is to be removed by qualified personnel ONLY! Heed all
caution markings indicating the presence of high voltage. High voltage may be up to 600V.
•
Test each circuit for short circuits before connecting it to relay so damage to the relay and its
electronics can be avoided.
•
Verify that all unused power supply leads are insulated with wire nuts.
•
Temperature rating of field-installed conductors to the main input of the panelboard section
are on the Listed Panelboard.
C copper wire at 75% ampacity.
o