UL-Data
The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general use
applications"
Ambient temperature:
Altidude:
Switching capacity:
Ambient temperature 55°C
Ambient temperature 40°C:
Wire connection::
PS-terminal:
PC-terminal:
PT-terminal:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo
Standard Type
UG 6960.04PS/100/61 DC24V 300 s
Article number:
• Safety function:
• Delay function:
• Time delay:
• Output:
• Nominal voltage:
• Width:
-15 ... +55°C
≤ 2000 m
Pilot duty B300, R300
5A 250Vac Resistive or G.P.
5A 24Vdc Resistive
Pilot duty B300, R300
8A 250Vac Resistive or G.P.
8A 24Vdc G.P.
60°C / 75°C copper conductors only
AWG 28 - 12 Sol/Str Torque 0.5 Nm
AWG 24 - 12 Sol/Str
AWG 24 - 16 Sol/str
0065424
e-stop
adjustable
adjustable
2 NO contacts instantaneous contacts
2 NO contacts delayed contacts
DC 24 V
22.5 mm
Variants
UG 6960 .04 _ _ / _ _ _ /61 DC 24 V 300 s
Troubleshooting
Failure
LED "ON" does not light up
LED "ERR" flashes
in relation 1:1
LED "ERR" flashes
in relation 4:1
LED "ERR"
continuously on
Maintenance and Repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
22
Max. time range or fixed time
Nominal voltage
UL-approval
Time delay
0 = Adjustable
1 = Fixed
Delay function
0 = Adjustable
Safety function
1 = E-stop,
with cross fault detection
2 = Safety gate,
with cross fault detection
3 = Two-hand control,
with cross fault detection
4 = Safety mat / Safety edge,
with cross fault detection
5 = Exclusive or contacts,
with cross fault detection
6 = E-stop,
without cross fault detection
7 = Safety gate,
without cross fault detection
8 = Light curtain,
without cross fault detection
Type of terminals
PC (plug in cage clamp):
pluggable terminal blocks,
with cage clamp terminals
PS (plug in screw):
pluggable terminal blocks,
with screw terminals
PT (plug in Twin cage clamp):
pluggable terminal blocks,
with cage clamp terminals 2-wire
Contacts
Type
Potential cause
- Power supply A1+/A2
not connected
- Under- or overvoltage
(check power supply A1+/A2)
- external failure (see flashing code)
- system error
(if cannot be removed after restart
unit must be replaced)
UG 6960 / 23.12.20 en / 352A