Service
Status on DI1 input
Status on DI2 input
Read temperature at sensor "Sc3"
Read temperature at sensor "Sc4"
Status on DI3 input
Status on DI4 input
Status on DI5 input
The controller can give the following messages
Error
E1
Fault in controller
message
E2
Regulation is outside the range, or the control
signal is defective
A2
Alarm
Low P0
message
A11
Refrigerant not selected
A17
High Pc
A19
DO 1 alarm. Terminal 29 is open
A20
DO 2 alarm. Terminal 30 is open
A21
DO 3 alarm. Terminal 31 is open
A22
DO 4 alarm. Terminal 32 is open
A23
DO 5 alarm. Terminal 33 is open
A24
DO 6 alarm. Terminal 34 is open
A25
DO 7 alarm. Terminal 35 is open
A26
DO 8 alarm. Terminal 36 is open
A27
Room temperature alarm (Saux1 temp.)
A28
DI 1 alarm. Terminal 46 interrupted
A29
DI 2 alarm. Terminal 47 interrupted
A30
DI 3 alarm. Terminal 49 interrupted
A31
DI 4 alarm. Terminal 50 interrupted
A32
DI 5 alarm. Terminal 52 interrupted
A34
Fan alarm. There is a signal on DI1 input
A45
Regulation stopped
S2
Status
Wait for "c01"
message
S5
Wait for "c07"
S8
Wait for "c11" or "c12"
S9
Wait for "c14" or "c15"
S10
Refrigeration stopped by the internal or external
start/stop function
S25
Manual control of outputs
S34
Safety cutout. Setting A30 is exceeded or all
safety inputs (29-36) are open
Info
PS
Access code is required before you have access to
the settings
EKC 531D1
u10
u37
u44
u45
u87
u88
u89
Instructions RI8HU452 © Danfoss 10/2006
Messages can be brought up on the display by briefly
pressing the uppermost key. If there is more than one alarm,
they can be scrolled through
Factory setting
If you need to return to the factory-set values, it can be done in
this way:
- Cut out the supply voltage to the controller
- Keep the upper and the lower button depressed at the same
time as you reconnect the supply voltage