Operation
Data communication
If the controller is extended with data communication, the opera-
tion can be performed from a system unit.
The importance of the alarms that are sent can be defined with
the setting: 1 (High), 2 (Medium), 3 (Low) or 0 (No alarm).
Operation via external display
The values will be shown with three digits, and with a setting you
can determine whether the pressures are to be shown in °C or in
bar. Or whether the temperature is to be shown in °F or in psig.
There are three options for the display.
EKA 165
EKA 163
EKA 164
The buttons on the display
When you want to change a setting, the upper and the lower
buttons will give you a higher or lower value depending on the
button you are pushing. But before you change the value, you
must have access to the menu. You obtain this by pushing the
upper button for a couple of seconds - you will then enter the
column with parameter codes. Find the parameter code you want
to change and push the mittle button. When you have changed
the value, save the new value by once more pushing the mittle
button.
EKC 531D1
You can connect this
display to the EKC
531D1 with software
version 1.3 or later.
Instructions RI8HU452 © Danfoss 10/2006
EKA 165
To operate the controller and view the evaporation pressure.
If the lowermost key is pressed, the condensation pressure will
be shown briefly in the display. (If regulation is based only on the
condensation pressure, the display will always show Pc).
During normal operation the light-emitting diodes in the display
will indicate where regulation is taking place.
Highest + second highest
Second highest
"None"
Second lowest
Lowest+ second lowest
The other LEDs on the display will show the functions that are
active:
• Relays for compressors
• Relays for fans
• Input signals for the digital inputs
• The optimisation LED will light up when the reference is 2 K or
more over the set point.
EKA 163
If the condensation pressure is to be shown constantly, a display
without operating keys can be connected.
EKA 164
To operate the controller and view the evaporation pressure.
If the lowermost key is pressed, the condensation pressure will be
shown briefly in the display.
Like the EKA 165, the LEDs in the display will show where the
regulation is located.
Or short:
1. Push the upper button (long push) until a parameter is shown
2. Push one of the buttons and find the parameter you want to
change
3. Push the mittle button until the setting value is shown
4. Push one of the buttons and select the new value
5. Push the mittle button again to conclude the setting
( A brief pushing wil show the active alarm codes.)
:
++Zone
:
+Zone
: Neutral zone
:
-Zone
:
- - Zone
5