Danfoss EKC 531D1 Instructions page 8

Masquer les pouces Voir aussi pour EKC 531D1:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Access code
Used sensor type for Sc3, Sc4 and "Saux1"
0=PT1000, 1=PTC1000
2-7=variations with temperature sensor on P0 and Pc. See 
earlier in the manual.
Set supply voltage frequency
Manual control of outputs:
0: No override
1-10: 1 will cut in relay 1, 2 relay 2, etc.
11-18: Gives voltage signal on the analog output. (11 
gives 1.25 V, and so on in steps of 1.25 V
P0 pressure transmitter's working range - min. value
P0 pressure transmitter's working range - max. value
Use of DI4-input
0=not used. 1=P0 displacement. 2=alarm function. 
Alarm="A31"
Operating hours of relay 1 (value time 1000)
Operating hours of relay 2 (value time 1000)
Operating hours of relay 3 (value time 1000
Operating hours of relay 4 (value time 1000)
Setting of refrigerant
1=R12.  2=R22.  3=R134a.  4=R502.  5=R717.  6=R13.  
7=R13b1.  8=R23.  9=R500.  10=R503.  11=R114.  
12=R142b. 13=User defined. 14=R32. 15=R227.  
16=R401A.  17=R507. 18=R402A.  19=R404A. 20=R407C.  
21=R407A.  22=R407B.  23=R410A.  24=R170.  25=R290.  
26=R600.  27=R600a.  28=R744.  29=R1270.  30=R417A. 
31=R422A.
Use of DI5-input
0=not used. 1=Pc displacment. 2=alarm function. 
Alarm="A32"
Pc pressure transmitter's working range - min. value
Pc pressure transmitter's working range - max. value
Read temperature at sensor "Saux1"
Operating hours of relay 5 (value time 1000)
Operating hours of relay 6 (value time 1000)
Operating hours of relay 7 (value time 1000)
Operating hours of relay 8 (value time 1000)
Selection of application
1. Temperature signal and "c16" mode
2: Pressure signal and "c16" mode
3. Temperature signal and M&M mode
4. Pressure signal and M&M mode
Function for relay output DO9:
0. Start / stop of speed regulation
1.  Inject on signal for evaporator control
2. Boost ready (at least one compressor is on)
3. Start /stop of condenser fan
Function for relay output DO10:
0. Alarm relay
1. Start / stop of condenser fan
Definition of alarm message at DI1 signal:
0. Not used
1. Fan failure (A34)
2. DI1 alarm (A28)
Definition of the signal to the P0 regulation when tem-
perature signal.
If frost protection is required, the setting must be 1 or 2.
0. Pressure transmitter AKA32R on P0
1. Temperature input Saux
2. Temperature input S4
Display connection
Off: EKA 164
On: EKA 165 (extended display with light-emitting diodes)
8 
o05
o06
o12
o18
o20
o21
o22
o23
o24
o25
o26
o30
o37
o47
o48
o49
o50
o51
o52
o53
o61
1
o75
o76
o78
o81
o82
Instructions  RI8HU452  ©  Danfoss  10/2006 
1 (0=OFF)
0
50 Hz
0
-1 bar
1 bar
0
0.0 h
0.0 h
0.0 h
0.0 h
0
0
-1 bar
1 bar
0.0 h
0.0 h
0.0 h
0.0 h
2
3
4
1
0
0
0
0
Off
100
OFF
7 (1)
0
60 H
0
18
0
0 bar
-1.0
60 bar
12.0
2
0
99.9 h
0.0
99.9 h
0.0
99.9 h
0.0
99.9 h
0.0
31
0
2
0
0 bar
-1.0
60 bar
34.0
99.9 h
0.0
99.9 h
0.0
99.9 h
0.0
99.9 h
0.0
4
1
3
0
1
0
2
0
2
0
On
Off
   EKC 531D1
°C

Publicité

Table des Matières
loading

Table des Matières