6.APPENDIX
Cable specification
1. Single phase unit
Nameplate
maximum
current
No more than 10A
10~16 A
16~25 A
25~32 A
32~40 A
40 ~63 A
63~75 A
75~101 A
101~123 A
123~148 A
148~186 A
186~224 A
2. Three phase unit
Nameplate
maximum
current
No more than 10A
10~16 A
16~25 A
25~32 A
32~40 A
40 ~63 A
63~75 A
75~101 A
101~123 A
123~148 A
148~186 A
186~224 A
When the unit will be installed at outdoor, please use the cable which can against UV.
Phase line
Earth line
2x1,5 mm
1,5 mm
2
2x2,5 mm
2,5 mm
2
2x4 mm
4 mm
2
2x6 mm
6 mm
2
2x10 mm
10 mm
2
2x16 mm
16 mm
2
2x25 mm
25 mm
2
2x25 mm
25 mm
2
2x35 mm
35 mm
2
2x50 mm
50 mm
2
2x70 mm
70 mm
2
2x95 mm
95 mm
2
Phase line
Earth line
3x1,5 mm
1,5 mm
2
3x2,5 mm
2,5 mm
2
3x4 mm
4 mm
2
3x6 mm
6 mm
2
3x10 mm
10 mm
2
3x16 mm
16 mm
2
3x25 mm
25 mm
2
3x25 mm
25 mm
2
3x35 mm
35 mm
2
3x50 mm
50 mm
2
3x70 mm
70 mm
2
3x95 mm
95 mm
2
MCB
Creepage protector
20 A
30mA less than 0.1 sec
2
32 A
30mA less than 0.1 sec
2
40 A
30mA less than 0.1 sec
2
40 A
30mA less than 0.1 sec
2
63 A
30mA less than 0.1 sec
2
80 A
30mA less than 0.1 sec
2
100 A
30mA less than 0.1 sec
2
125 A
30mA less than 0.1 sec
2
160 A
30mA less than 0.1 sec
2
225 A
30mA less than 0.1 sec
2
250 A
30mA less than 0.1 sec
2
280 A
30mA less than 0.1 sec
2
MCB
Creepage protector
20 A
30mA less than 0.1 sec
2
32 A
30mA less than 0.1 sec
2
40 A
30mA less than 0.1 sec
2
40 A
30mA less than 0.1 sec
2
63 A
30mA less than 0.1 sec
2
80 A
30mA less than 0.1 sec
2
100 A
30mA less than 0.1 sec
2
125 A
30mA less than 0.1 sec
2
160 A
30mA less than 0.1 sec
2
225 A
30mA less than 0.1 sec
2
250 A
30mA less than 0.1 sec
2
280 A
30mA less than 0.1 sec
2
Signal line
nx0.5mm
2
Signal line
nx0.5mm
2
24