The main burner flame and pilot burner flame must be
checked for proper flame characteristics, as outlined in the
Installation Instructions and Owner's Manual.
Verifying Input Rate of Converted Fireplace
The input of the fireplace must be checked as follows:
1. Turn off all other gas appliances. Clock the gas meter
and determine the number of seconds required to
consume one cubic foot of gas.
2. 3600 ÷ time (in seconds) = cu. Ft. per hour.
3. Then cu. Ft. per hour x heating value of gas = input
rate (Btuh). On installation without gas meters, check
manifold for proper pressure.
41336-0-1119