NAVIGATION
Navigation is achieved by selecting any of the desired parameters.
Settings can be changed via number of inputs or sliders.
NOTE: For Fixture manufacturers, Wattstopper recommends that you do not create a Jobsite and Password when preprogramming
devices at the assembly line. In addition, disregard the above notice about the Bluetooth low energy technology stopping
broadcast after seven days, since this only happens if the device is not power cycled for seven days.
The steps below are used to verify that the sensor is wired and operating correctly. The extent of the testing is at the discretion of the
installer, who is most cases is the fixture manufacturer.
1. The first time the sensor is installed and powered, there will be 50 seconds of warm-up. The load will turn OFF after the warm-up
time if no motion is detected. To test functionality further, proceed to steps below
2. Log in to the Sensor Config App, then tap Device Discovery. The Devices screen opens and displays a list of sensors along with
their signal strength.
3. Tap a sensor. The loads connected to that sensor will flash ON and OFF, to give a visual indication of which sensor you are
communicating with. After a few seconds, the Device Security screen opens.
4. Turn the Select Jobsite switch Off.
This allows you to test the sensor
without having to store a password in
the sensor. Then tap Submit.
5. Tap the Controls option. The
parameters on this page are used for
testing the sensor. Additionally, the
current amount of light registered by
the light level sensor, as well as the
sensor's firmware version is displayed.
6. Tap Test Mode. This mode shortens
timeouts for High/Low and Cut Off,
to allow quick verification of settings.
You can set the length for test mode
(default is 3 minutes). Range: 1 to 5 minutes. Tap Start to enter test mode.
7. If you tap Dimmer Level, the screen shows the current dimming level (from 0V to 10V). You can temporarily change the dimming
level for testing purposes by dragging the slider or tapping the "+" or "–" buttons. The level will change to the specified amount for
several seconds, then revert to the previous amount.
TESTING THE FDP‑301SR WITH THE SENSOR CONFIG APP
Turn Select Jobsite Off
RESETTING THE FDP‑301SR
The FDP-301SR has two different reset functions.
• Hold the reset button under the sensor lens for 5 seconds
to reset the password. A single flash indicates the reset has
occurred. This allows you to assign a new password for
use with the Sensor Config app.
• Hold the reset button for 10 seconds to reset all
FDP-301SR parameters to default values. Two flashes
indicate a full reset. This will also reset the password.
Select Controls
3
Controls Menu for Testing