MASKING THE LENS
The optional FDP-M1 mask provides
the ability to limit coverage areas for
example, in hallways or multi-use
environments. The mask has three 90°
sections. One or two of the sections
can be removed, to provide different
coverage patterns. Snap the mask
onto the lens and rotate to the desired
position.
The FDP-301SR has a 4-pin twist-lock NEMA connector that attaches to a 4-pin receptacle*.
The receptacle mounts into the fixture and is wired to the driver, as listed in the table below.
Mounting the sensor is then simple—insert the pins on the connector into the receptacle,
and rotate clockwise to lock. the connector only fits onto the receptacle one way, so the pins
always line up correctly.
*Part 2213858-1, sold separately
Pin
1
not used
2
DALI (or DALI-based protocol) - / common ground
3
DALI (or DALI-based protocol) +
4
not used
WARNING: TURN THE POWER OFF AT
THE CIRCUIT BREAKER BEFORE WIRING.
The Sensor Configuration App is available for both iOS
on your device to download.
NOTE: Bluetooth communication ranges can vary depending on the device, as well as mobile carrier. Wattstopper
recommends devices with Bluetooth 5.0. Iphone 8 and Samsung Galaxy S8 and later devices are
recommended for optimal performance.
The Sensor Configuration tool is a mobile app for changing defaults and testing of the FDP-301SR. It provides
wireless access to the FDP-301SR sensors for parameter changes and testing. Within a certain mounting
height of the sensor, the Sensor Configuration app allows modification of the system without requiring
ladders or tools.
If no configuration steps are taken, the sensor will use its default parameter values.
The Sensor Configuration app display shows menus and prompts to lead you through each process. The
mobile app provides a simple way to navigate through the customization fields.
The Sensor Configuration app allows bi-directional communication between the FDP-301SR and the
mobile app. Simple menu screens let you see the current status of the sensor and make changes. It can
change FDP-301SR sensor parameters such as high/low mode, sensitivity, time delay, cut off and more.
With the Sensor Configuration app you can also establish and store FDP-301SR parameter profiles and
enable continuous dimming.
The Sensor Configuration mobile app has the ability to detect multiple sensors based on signal strength or
distance.Every time the commissioning tool establishes communication with the FDP-301SR, the controlled
load will flash, providing a visual indication of which FDP-301SR you are configuring.
For details on the features and operation, download the Config App User Guide from the wattstopper web
site at :
https://www.legrand.us/wattstopper.aspx
NOTE: The Bluetooth low energy technology radio stops broadcasting after 7 days of being powered on if
no password is set for the device. Cycling the power turns the Bluetooth radio back on.
IMPORTANT: We recommend that you secure the sensor with a jobsite password. Do not lose your jobsite password. Jobsite
passwords are stored on the app on the phone that was used to commission the sensor. Forgetting the password or not sharing with the
appropriate authority will require you to reset the FDP-301SR in order to communicate with it.
MOUNTING AND WIRING
Function
FDP‑301SR CONFIGURATION WITH THE SENSOR CONFIG APP
PIR Sensor
®
®
and Android
devices. Search "Wattstopper Sensor Config"
2
FDP‑301SR COMPONENTS
Motion Indicator
Blue LED
Light Sensor
4-pin Receptacle
4--pin Connector
Twist to lock
Reset Button
Driver
Bottom of
Fixure

Publicité