TX507/TX510/TX513
EN
Quick Start Guide
HMI-TX507/TX5010/TX513
Product description
The HMIs (Human Machine Interfaces) of the TX500 series combine control,
operation and monitoring in a full-scope control thanks to the CODESYS V3 PLC
with integrated visualization.
Dimensions and cut-out
See fig. 1
A
B
TX507
176 mm/
136 mm/
06.90"
05.35"
TX510
276 mm/
221 mm/
10.86"
08.70"
TX513
326 mm/
256 mm/
09.30"
10.1"
Applying the gasket
TX507: see fig. 2
TX510 und TX513: see fig. 3
A
Gasket
B
Installation cut-out
Fixing bracket
See fig. 4
Note
Screw each fixing screw until the bezel corner gets in contact with the panel.
Connectors and slots
See fig. 5
1
Serial port
Ethernet ports
2
3
USB port (version 2.0 - 1.1)
4
USB port (version 2.0 High speed only)
5
Power supply
6
Expansion slots for plug-in module
7
SD card slot
NOTE
Devices of protection class III according to EN 61140 or Class 2 according to UL
standards: All connections are SELV connections.
DANGER
USB-port not intrinsically safe
Danger to life due to risk of explosion!
Do not use the USB-port in hazardous locations.
Power supply
See fig. 6 and 7
DANGER
Wrong selection of power supply
Danger to life due to overvoltage and electric shock!
Only operate devices at SELV-power supplies.
ATTENTION
Unprotected electronic circuits
Destruction of electronics!
Do not open the device under voltage.
NOTE
Ensure that the power supply has enough power for the operation of the
equipment.
Serial port
see fig. 8
Pin
RS232
1
GND
2
n.c.
3
TxD
4
RxD
5
n.c.
6
+5 VDC output
C
H
L
47 mm/
147 mm/
187 mm/
01.85"
05.79"
07.36"
56 mm/
232 mm/
287 mm/
02.20"
09.13"
11.30"
56 mm/
267 mm/
337 mm/
02.20"
10.51"
13.26"
RS485
RS422
GND
GND
n.c.
n.c.
A
Tx -
Rx -
n.c.
n.c.
+5 VDC output
+5 VDC output
Pin
RS232
7
CTS
8
RTS
9
n.c.
NOTE
In case of using the interface as RS485-interface, pin 3 and 4 as well as pin 7
and 8 have to be connected externally.
Expansion slot for Plug-in modules
UL-conformity can only be guaranteed if UL-conform plug-in modules are used.
Dispose of batteries
Position of the battery, see fig. 9
NOTE
Dispose batteries according to local regulations.
Approvals and standards
The products have been designed for use in Hazardous Location according
ANSI/ISA-12.12.01.
The products have been designed for use in an industrial environment in com-
pliance with the 2014/30/EU directive .
Compliance
The products have been designed in compliance with:
EN 61000-6-4/ EN 61000-6-2
EN 61000-4-2 to -4-6, EN 61000-4-8
EN 55011, Class A
EN 60945
ATTENTION
Operation in
residential and commercial areas
Electromagnetic disturbances!
In case of the operation of the devices in residential and commercial areas,
observe the measurement values according to IEC-61000-6-3.
Safety notes for the operation in hazardous areas (only approved in
USA and Canada, no ATEX Certification!)
NOTE
The Power, input and output (I/O) wiring has to be done in accordance with
Class I, Division 2 and in accordance with the authority having jurisdictions. For
U.S. in accordance with Article 501.10 (B) of the National Electrical Code, NFPA
70 and for Canada in accordance with Section 18-1J2 of Canadian Electrical
Code.
DANGER
Loss of Class 1, Division 2 approval in case of substitution of components
Danger to live due to risk of explosion!
Do not use components which do not comply with the Class 1, Division 2
certification.
DANGER
Replacing or wiring modules under voltage
Danger to live due to risk of explosion!
Switch-off the device before replacing or wiring modules.
DANGER
Disconnecting devices under voltage
Danger to live due to risk of explosion!
Do not disconnect devices under voltage, as long as they are installed in
ignitable atmospheres.
NOTE
The devices are suitable for the use in Class 1, Division 2, groups A, B, C and D
(hazardous locations and non-hazardous locations).
DANGER
Replacing the battery
Danger to live due to risk of explosion!
Do not replace the battery as long as they are installed in ignitable atmo-
spheres.
© Hans Turck GmbH & Co. KG | D301395 2016-06 DE EN FR