3
Connect the batteries to the power
supply terminals (3) using the
correct wire complete with
protection with fuse.
Be careful with the battery
polarity during the
connection.
This information expands that of page 61 of manual T8741A:
burglar-alarm system – installer's manual.
The following table gives the maximum absorption which the system must have
depending on the battery installed and the life-time level required.
In all cases the maximum absorption must not exceed 700 mA.
lifetime when
there is
a power cut
(
) In these cases the system respects level 1 of standard IEC 79-2.
*
Note: use siren 4072A with week of production later than 29 of 2005.
Install the container closing
covers
type of battery installed
7,2 Ah
110 mA ( * )
24 h
180 mA
15 h
8 h
340 mA
If you want to protect the battery compartment,
connect the contact on the container item
F115/8B (4) to a tamper line.
12 Ah
24 Ah
190 mA ( * )
380 mA
300 mA
600 mA
560 mA
700 mA
4
4
5