3. CONNECTIONS
3.1. CONNECTIONS
OPEN THE "RT COM" TIME BASE:
Open the terminal box which have inside the 6 black terminal
►
►
Connect the wires n°2 and n°4 to the GND terminal on the position sensor input
terminal block.
►
Connect the wire n°5 to the "MIN" terminal.
►
Connect the wire n°3 to the "12 Hrs" terminal.
connect the sensor wires between the GND and MIN terminals.
►
Open the terminal box labelled "230Volts":
►
Connect COM to COM, A to P1 and B to P2 on the motor control terminal block.
►
Connect the 230 VAC power supply to the "Entrée Alim. 230Volts" terminal, taking
care to connect the "TERRE" wire in the middle.
3.2. CONTROL AND MONITORING DEVICES
LD1: Mains present indicator light
LD2: Light indicating synchronisation with the received code:
►
Lights as soon as the received code is correct.
►
Flashes if there is temporary interference of the received code.
►
Light off when there has been no code for 24 hours.
LD3: Light indicating monitoring of the received code:
►
Flashes as the synchronisation code is received.
SW1: Switch for resetting the hands to midday
►
ON: Position fixed at midday
►
OFF: Automatic time reset starting at midday.
MAN P1 and MAN P2: Manual motor forward operation keys.
SW2: Switch for programming the time zones
MDE-RTcom-3024V1.5
AND CONTROL AND MONITORING DEVICES
☛
Note: For clocks with minute control only,
(for tests only)