LEGRAND 608 65 Mode D'emploi page 15

Table des Matières

Publicité

Special functions (continued)
Temporary postponement of the test day
In circumstances where the test area is occupied at an unusual time, the test time may be inconvenient for
that activity, and it is possible to postpone all the tests due to take place that day for 24 hours.
- Press the "ALLUMAGE" (ON) button on the 039 01 unit :
its LED illuminates for 6 seconds and then goes out.
- In the 3 seconds after the LED goes out, press the "ALLUMAGE" (ON) button again : its LED illuminates for
6 seconds and then goes out.
- Press the ON button a third time within 3 seconds.
Note : In the case of a mixed installation comprising some units which cannot be tested automatically :
- Wait 3 seconds, then end by pressing the "EXTINCTION" (OFF) button on the 039 01.
All units which were due to light up in the next 24 hours have their test put back by one day. The programme
then resumes its normal routine
Extended period without use
(eg. seasonal operation) After a long switch-off period, the batteries may well have discharged completely
and the programming may be lost. When switched on again, the unit LEDs will flash green/orange to indicate
this fault. The unit vill require reprogramming.
Definitive postponement of the test day
Follow the same procedure as for choosing the test time.
Stopping a test in progress
If a standby power test interferes with operation, it can be stopped immediately. Press the "EXTINCTION"
(OFF) button on remote control unit 039 01. The test is cancelled and postponed until the next day.
Exception
When the power is switched off for more than 3 days, the tests are no longer performed. The test cycle is
resumed after the power has been restored and the batteries have been recharged. The tests scheduled for
that day are automatically put back by 24 hours.
Maintenance
1 - Safety lighting tube
2 - Pilot light
3 - Batteries
Safety lighting tube
Replacing and checking the tube, when a safety lighting
fault is indicated (orange LED flashing quickly) :
- Remove the diffuser
- Replace the tube
- Check operation by pressing the test button quickly
- The tube illuminates for 6 seconds
- If the repair has been carried out correctly :
- the orange LED goes out ;
- the green LED illuminates.
Note : If the test button is pressed momentarily when no safety lighting fault is indicated (green LED
illuminated), the tube lights for one hour.
1
TL 8W G5 E 10
≥ 430 Lm
12 V
608 65
3W
TL 8W G5
608 66
≥ 430 Lm
21
2
Saft VTD 70 series 137
Energizer ETL 4000D
Panasonic P 400 DH
idem
3
4 x 1,2V
4 AH
KRMT
33 / 62 NiCd
idem

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

608 66

Table des Matières