SECTION 6 |
operating
threshold/
condition/
reason
protection
No Output
Internal hot
due to High
spot > 88°C
Temperature
to 115°C
Shut Down
No output due
Output power
to Over Load
is > Continu-
Shut Down
ous / Surge
Rating
No output due
Neutral or
to Ground Fault
Line con-
Shut Down
nected to
Ground
No output
No DC Input
Voltage due
to Blown DC
Input Fuse
For
15A breaker
SAM-2000-12,
on top of the
SAM-3000-12:
outlet has
No output
tripped due to
from outlet to
load > 1725
which load is
VA/15A
connected
* On activation of protection, the Green LED will start dimming slowly and will extinguish after some time.
Protections Monitoring
& Trouble-Shooting
Green
yeLLoW
LeD (6,
LeD (5,
power)
input
fault)
OFF*
ON
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
reD
Buzzer
LeD (7,
fault)
OFF
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
SAMLEX AMERICA INC. | 23
remedy/reset
Check ambient tempera-
ture, fan and loss of cool
replacement air .
Auto reset when hot spot
cools down 10°C to 15°C
below the threshold.
Check starting surge rating
of load. If happens with
low power CFL or SMPS, try
adding small resistive load.
If happens when inverter
is switched ON with high
capacitance load already in
ON condition, try switching
ON the load 10 sec after the
inverter has been switched
ON.
Manual Reset. Unit will latch
in shut down condition. To
reset, switch OFF the ON/
OFF Switch, wait for 3 min-
utes and switch ON again.
Check if there is Neutral to
Ground bond or Ground
Fault.
Manual Reset. Unit will latch
in shut down condition. To
reset, switch OFF the ON/
OFF Switch, wait for 3 min-
utes and switch ON again.
Check fuse in the 12V bat-
tery input line.
Remove the load and reset
the breaker (push in).
Ensure load connected to 1
outlet is < 1725 VA/15A.
Use 2 outlets in parallel if
load is > 1725 VA.