Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Protection unit

11. Menu navigation

L1:
O A
OA
L2:
L3:
OA
N:
OA
OK
1/6
protections
state
modules
system para.
archives
continue to page 48
state 2/6
1/1
(current
(curren t
protection)
protection)
long time
OK
OK
short
instant.
(curren t
protection)
long time
short
instant.
(curren t
protection)
long
short
instant.
neutral protec.
ground protec.
neutral protec.
ground protec.
only for versions with ground protection
1/5
long time
IR=1600A
to modify by knob
(100.0%In )
OK
time
long time
TR=C3
( 20s @6.0IR
to modify by knob
thermal-mem.
on
)
2/5
t=k
I=12800 A
to modify by knob
OK
( 8.0
IR
×
time
T=0.5s
)
3/5
instant.
I=24000 A
to modify by knob
time
OK
(
)
15.0×In
time
4/5
neutral protec.
OFF
to modify by knob
OK
5/5
ground protec.
OFF
to modify by knob
OK