Ygnis BLU 7000.1 PR Manuel D'instructions page 11

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SELECTOR
COMMUTATORE
AUTO
0
operating elements locked in an intermediate
0 = bloccaggio degli apparati per il
position
funzionamento in una posizione intermadia
= funzionamento alla massima potenza
operation on maximum capacity
= funzionamento alla minima potenza
operation on minimum capacity
AUTO = funzionamento automatico
automatic operation
AD J U STI N G TH E M I N I M U M CAPACI TY O F TH E BU RN ER – AI R and G AS
Position the selector placed on the control panel on position 2 and proceed as follows:
Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gas flow,
as established by analyzing the combustion process.
Position the selector, situated on the control panel, on position 1 and proceed as follows:
Adjusting the maximum gas flow rate (see figure on solenoid valve adjustments) or adjust the gas pressure in the gover-
nor.
Adjusting the maximum air flow rate (see figure, detail 2). Loosen the nut holding the air damper transmission rod;
The correct air flow as established by analyzing the combustion process.
Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the position of
the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
CALCULATING THE BURNER CAPACITY
To calculate the burner's capacity in kW, proceed as follows: Check the gas flow rate (in liters) on
the counter and the time of the reading in seconds.
Proceed with the calculation using the following :
AI R AD J U STM EN T
Part. 1
-
-
+
Part. 2
AD J U STI N G TH E M AXI M U M CAPACI TY O F TH E G AS
AD J U STI N G TH E M AXI M U M AI R FLO W RATE
AD J U STI N G TH E I N TERM ED I ATE BU RN ER CAPACI TY
420010391600 BLU 7000. 1 - 12000. 1 PR / M D
e x f = kW
s ec
pag.11
B
- -
+
Part. 3
e
= Litres gas
sec = Time in second
G20 = 34,02
f
G30 = 116
G31 = 88