Hazardous (Classified) Location
Class I, Division 1, Group A,B,C,D
Class I , Zone 0 and 1, Group IIC
Class II, Division 1 Group E, F, G
Intrinsically safe apparatus
entity parameters:
Vmax. (Ui) ≥ Voc (Uo)
Imax. (Ii) ≥ Isc (Io)
Pi ≥ Po
Ca ≥ C
+ Ci
cable
La ≥ L
+ Li
cable
The sum of capacitance and inductance of cable and
intrinsic safe equipment must be less or equal to Ca and La
Installation notes:
1) The maximum nonhazardous location voltage is 250 VAC/DC.
2) The installation shall be in accordance with the National Electrical Code NFPA 70, Articles 504 and 505.
3) The terminals of the two individual channels shall not be interconnected in any way.
4) Install in Pollution degree 2 or better
5) Use 60 / 75 °C copper conductors with wire size AWG: (26 – 14).
6) Warning: Substitution of components may impair intrinsic safety.
UL control drawing 5105QU01
+
V
-
Voltage or
current output
+
V
-
5105B Associated apparatus parameters
CH1
Terminals 41 to 43
CH2
Terminals 51 to 53
Voc (Uo) 28 V
Isc (Io)
93 mA
Po
0.65 W
IIC / grp. A,B IIB / grp. C
Ca (Co)
0.052 μF
La (Lo)
2.4 mH
5105BV105-FR
Non-hazardous
Associated apparatus
Galvanically isolated
31
33
43
+
42
mA
-
41
CH1
53
+
52
mA
-
51
5105B
CH2
0.44 μF
12 mH
13
+
12
V
+
-
-
11
23
+
22
V
+
-
21
-
IIA / grp.D
1.45 μF
20 mH
Rev. AA 2003-02-12
15