en
7.1.3
Stage selection by reverse polarity (TAR) - all DC versions (except option –SSM)
Note:
Only applicable to DC version!
Not applicable to –SSM versions!
The control inputs C1 and C2 must not be connected on the connection board!
Switch setting should be as follows:
S1A to
(diode bridged)
and changeover switch S1B to "+"
Tone "C1+C2" can also be selected by reversing the polarity of the operating voltage to the basic tone (♪):
8. Option
–SSM (soft-start module, only 24V DC)
The inrush current peak is limited to:
: max. 2.1 A
The operating voltage is only switched through to the operating equipment from >7 V.
Operating voltage range: 18 V – 30 V DC
Positioning of the resistor (1kOhm) is as follows:
Always mount the resistor for line monitoring in the last device.
See below for the position of the second resistor if the sounder and flashing light are connected separately.
Remove any resistors that are not required.
Common connection of sounder and flashing light:
Separate connection of sounder and flashing light:
06/2020
Operating instructions PA 1 / PA X 1-05
Base tone
:
max. 2.1 A
Page 10 / 11
(on the driver board)
Tone "C1+C2"