11 BACnet

General information and BIBBs

Communication
BACnet MS/TP
BACnet IP
Information device
General information
BIBBs
BIBBS BACnet Interoperability
Building Blocks supported
Propriété de SDATAWAY SA- © 2018 SDATAWAY SA Tous droits réservés. Page 38 / 39
Medium
Transmission formats
Baud rates
Termination
IP address assignment
Parametrization
Vendor Name
Vendor Identifier
BACnet Protocol Revision
BACnet Standard Device
Profile
Segmentation Capability
Data Link Layer Options
Device Address Binding
Character Sets Supported
Network Security Options
DS-COV-B
DS-RP-B
DS-RPM-B
DS-WP-B
DS-WPM-B
DM-DDB-B
DM-DOB-B
DM-DCC-B
DM-RD-B
Système EasyBus3®
Documentation Technique
RS-485
1-8-N-1, 1-8-E-1 and 1-8-O-1
(start bit, data bits, parity, stop
bits)
9600, 19200, 38400, 57600,
115200
With/Without
Static or DHCP
Device menu
SDATAWAY
1201
12
BACnet Application Specific
Controller (B-ASC)
Both
MS/TP master Baud Rates:
9600, 19200, 38400, 57600,
115200
BACnet IP master
Static or DHCP
ISO 10646 (UTF-8)
Non-secure device
Data Change of Value-B
Data Sharing-Read Property-B
Data Sharing-Read Property
Multiple-B
Data Sharing-Write Property-B
Device Management-Dynamic
Device Binding-B
Device Management-Dynamic
Object Binding-B
Device Management-Device
Communication Control-B
Device Management-
Reinitialize Device-B