left key and then set the value with the
right key.
g.
To switch to the next menu item, keep the
left key depressed and press the right key
h.
Selecting "Yes" in the last menu title "End-
Pro" allows exiting the programming menu
and taking over (saving) the new values. If
"No" is selected, the programming routine
restarts from the beginning; the last values
set are maintained. They can now be
modified once more or checked.
4. Programming routine
The settable parameters of the device are
listed below, in the order in which they will be
set. Thus, the device is entirely set after com-
pletion of the routine.
The top symbol always corresponds to the
factory setting.
4.1 Input signal range (measuring range)
0...20 mA
4...20 mA
0...10 V
2...10 V
4.2. Measuring time
0.5 sec
0.1 sec
Page 3 (R60046.0009 - Index 1)
4.3 Decimal point setting
The decimal point defines the
number of displayed decimal
places for the current mea-
sured value (only for display
purposes).
0
0.0
0.00
0.000
0.0000 four decimal places
4.4 Minimum input signal
This menu item allows exten-
ding or reducing the measu-
ring range.
If the input signal becomes lower than the
value programmed here for the measuring
range
4...20 mA, min. 3.5 mA, default 4 mA
0...20 mA, min. -0.5 mA, default 0 mA
2...10 V, min. 1.5 V, default 2 V
0...10 V, min. -0.5 V, default 0 V
is displayed,
the display alternates between „Lo" and the
measured value.
Below the min. programmable measuring
value, -1.9.9.9.9 is displayed to signal an
underflow.
4.5 Display value for the lowest input signal
A value to be displayed bet-
ween -19999 and 99999 can
be assigned to the lowest
input signal (0V, 2V, 0mA,
4mA). The decimal point set-
ting is taken into considera-
tion (e.g. range 0...10V, this
programmed value is issued
for 0V).
no decimal place
one decimal place
two decimal places
three decimal places