LK 810 ECO Loading Unit | Mounting and Operating Instructions
General Information
LK 810 ECO is an automatic loading unit for solid-fuel boiler/storage tank installations. The loading unit ensures a
minimum return-water temperature into the heating boiler, which increases boiler efficiency, prevents tarring and
considerably prolongs the lifetime of the heating boiler.
LK 810 ECO eliminates the risk of destructive thermal shock caused by surges of cold return water and renders a
more effective burning. The heating boiler quickly reaches the right working temperature. In the end phase of the
firing an automatic balancing valve closes the by-pass loop. This results a maximum cooling of the boiler and the
storage tank is fully filled with hot water.
LK 810 ECO automatically allows self-circulation as soon as the fire has gone out so that the rest of the heat in the
boiler is transferred into the storage tank. It also allows self-circulation in case of power failure.
LK 810 ECO loading unit is normally service free. The valve unit has three ball valves. Any part can be changed
without draining the system.
Technical Data
Voltage
Power consumption
Thermostatic elements
Max. boiler capacity
Max. operating temp.
Max. operating pressure 1,0 MPa (10 bar)
Circulation pump
Max. flow
Sizes
Body
Dimensions
Weight
Mounting
The valve unit is mounted upright either on the right- or left-
hand side of the heating boiler. The thermometers are pressed
onto the front side of the unit.
For a trouble free system the piping work must be done without
air pockets. If this is not possible the system must be fitted with
air vents.
Several boilers have integrated thermostats for pump control. If
not, a flue gas thermostat must be installed. The circulation pump
should start at the same time as the firing. The pump should stop
soon after the fire has gone out to let the remaining hot water in
the boiler self-circulate to the storage tank.
230 VAC 50 Hz
Min. 5 W
Max. 45 W
For 55°C, 60°C, 65°C and
70°C return temperature.
Other temperatures on demand
75 kW with 55°C element
65 kW with 60°C element
50 kW with 65°C element
35 kW with 70°C element
110°C
Grundfos Alpha 2L 60
2300 l/h
Rp 1", Rp 1¼" or 28 mm
compression fittings
NPT threads available
Brass EN 1982 CB752S
210 x 210 x 110 mm
4,8 kg
LK 810 Laddpaket | Monterings- och bruksanvisning
Installation
Laddningspaketet är vändbart och installeras antingen till höger eller vänster om pannan. Termome-
trarna monteras sist.
För att funktionen av anläggningen skall vara problemfri, måste installationen utföras så att ingen luft
fi nns i värmesystemet.
I vissa fabrikat av pannor fi nns en termostatfunktion för att starta och stanna laddningspumpen. Till
pannor som ej har någon färdig termostatfunktion rekommenderas en rökgastermostat. Laddnings-
pumpen startar när eldningen påbörjas och stannar när eldningen uppför.
Vänstermontage
Tank
Backventilens Funktion
Main Parts:
1. Thermally operated loading valve
2. Automatic balancing valve
3. Backflow preventer, depending on model
4. Circulation pump, Grundfos Alpha 2L 60
5. Three thermometers
6. Three ball valves
7. Insulation EPP
Dimensioning
Pipe dimensioning between heating boiler and
storage tank:
• LK 810 ECO loading unit with Rp 1" ball valves.
For heating boilers up to 35 kW ..... DN 25
Installation
• LK 810 ECO loading unit with 28 mm ball valves.
Laddningspaketet är vändbart och installeras antingen till hö
For heating boilers up to 35 kW .... DN 28
trarna monteras sist.
För att funktionen av anläggningen skall vara problemfri, må
• LK 810 ECO loading unit with Rp 1¼" ball valves.
fi nns i värmesystemet.
I vissa fabrikat av pannor fi nns en termostatfunktion för att s
For heating boilers up to 75 kW ... DN 32
pannor som ej har någon färdig termostatfunktion rekomme
pumpen startar när eldningen påbörjas och stannar när eldni
Storage Tank
Backventilens Funktion
LK 810 laddningspaket har, beroende på modell, en inbyggd b
cirkulation när laddningspumpen inte är i drift. Backventilen h
1.
2.
3.
Backventilsfunktionen kan vid behov blockeras. Backventilen
Heating Boiler
Se sida 22-23, del 13.
Panna
Funktion
LK 810 Laddpaket | Monterings- och bruksanvisning
Left-hand mounting
Vänstermontage
Tank
Panna
Heating Boiler
Right-hand mounting
Högermontage
Vid avslutad eldning kan restvärme från pannan självc
Vid strömavbrott kan värmen i pannan självcirkulera t
Förhindrar återcirkulation från tanken till pannan.
Storage Tank
Panna
Tank