Current transformer

Operating Instructions
!
WARNING
HAZARDOUS VOLTAGE.
Can cause electrical shock
and burns.
Disconnect power before proceeding
with any work on this equipment.
Reliable functioning of the equipment is only ensured with certified
components.
!
Limited protection against contact with live parts
Degree of protection IP00 according to IEC 60529, DIN 40050.
Shock protection between current transformer and contactor by addi-
tional terminal covers.
Commissioning and maintenance by qualified personnel only.
Follow the operating instructions!
Current transformer must not be operated without a
!
load on the secondary side!
Application
The 3UF18 current transformer can be used as a lineside transformer
for the SIMOCODE-basic unit 3UF10 and 3UF20 (see Fig. IVa) or for the
3UB11 electronic overload relay (see Fig. IVb). Other applications are
also possible.
Installation
Direct assembly with contactor. Separate installation is required in
case of strong vibrations.
For dimension drawings see Fig. I to Fig. III (dimensions in mm).
Protection against electric shock according to VDE 0106, Part 100, for
transformer connections by additional terminal covers.
Current
Working range of
transformer
transformer
[A]
3UF18 47
16 to 65
3UF18 48
25 to 100
3UF18 50
32 to 130
3UF18 52
50 to 200
3UF18 54
63 to 250
3UF18 56
100 to 400
3UF18 57
125 to 500
3UF18 68-3F
160 to 630
3UF18 68-3G
205 to 820
4
Type of
Transformation
contactor
ratio
3TF 46/47
65 : 1
3TF 48/49
100 : 1
3TF 50
130 : 1
3TF 51/52
200 : 1
3TF 53/54
250 : 1
3TF 55/56
400 : 1
3TF 57
500 : 1
3TF 68
630 : 1
3TF 69
820 : 1
Order No.: 3ZX1012-0UF18-1BA1
Terminal cover B can be cut to required length; can also be assembled
directly with the transformer.
For separate installation use the second box terminal (for
3UF1847 to 3UF1850). For snapping onto mounting rail use base
plate A (for 3UF1847 to 3UF1852).
Minimum clearances to earthed parts see Fig. I and II ¿ !
Can be mounted in any position.

Technical Data

Accuracy
max. secondary loading (burden)
Conductor length between trans-
former secondary side and
- 3UF
- 3UB
Relevant standards
Permissible ambient temperature:
- Operation
- Storage
Rated
Rated insulation voltage U
frequency
IEC/VDE 0110, 0660
[Hz]
50/60
1000
3UF1847 ... 3UF1868
DIN VDE 0660, IEC 60947
English
± 3 %
100 m
2
4 m
for
2.5 mm
@
2
2,5 m
for
1.5 mm
@
2
6 m
for
2.5 mm
@
2
3.5 m
for
1.5 mm
@
DIN VDE 0660 Part 104
IEC 60947-4
DIN 57165
UL 508
CSA C22.2
–25 to +60 °C
–40 to +85 °C
[V]
Weight
i
[kg]
UL/CSA
600
1.2
1.3
1.5
1.6
3.8
4.0
4.5
7.6
8.2