5.4.2 Measuring method

Selection in the menu
5.4.3 Decimal point
Decimal point
Selection in the menu
Resolution 0,1 °C/0,1 °F
Resolution 1 °C/1 °F
5.4.5 Correction value
Inputting a correction value allows acting upon the dis-
played result. These correction values may be
Setting the correction value
Selection in the menu
...
5.4.6 Maximum value acquisition
The maximum value may be saved and consulted during
operation (see 6.1)
Selection in the menu
Maximum value acquisition on
Maximum value acquisition off
14
Measuring method
2 wires; please note
See point 5.4.2.1 oppo-
site!
3 wires
4 wires
...
5.4.2.1 Line resistivity
If you selected the 2-wire measuring method in 5.4.2, the
display shows
Input here the line resistivity of your 2-wire probe for
long connection cables. If the resistivity value input
here is wrong, the displayed result will not be cor-
rect.
...

5.4.4 Temperature unit

Unit
Selection in the menu
Display in °C
Display in °F
positive or negative. The input is always made with one de-
cimal place.
Correction value in 0,1 °C/0,1 °F,
depending on the unit selected
5.4.6.1 Resetting the maximum value
This allows defining whether the maximum value can be
reset during operation or not. However, the maximum value
can only be reset if the maximum value display is the active
function (see 6.1). If the maximum value is reset, the cur-
rent measured value becomes the new maximum value.
Selection in the menu
The maximum value can be reset
using the red key
The maximum value cannot be reset
line resistivity