SURFACE MOUNTING:
(Mounting to Ø 60 mm connector socket possible)
► To run cables in from the side, drill where marked.
► Screw the wall mounting base firmly to the wall.
► Run in the cable and connect it.
► Screw the BMK-Touch to the wall mounting base.
► Clip on the cover.
FLUSH MOUNTING:
(Flush-mounting box, part no.: 2747871, required)
Note: Use screws and clips on plasterboard wall.
► Break out the tab from the cable inlet on the flush-mounting box.
► Mount the flush-mounting box in the wall.
► Run in the cable and connect it.
► Screw the BMK-Touch to the
flush-mounting box.
► Clip on the cover.
SPECIFICATION:
Power supply:
Maximum power
consumption:
Max. line length
with AWG22 twisted pair:
IP rating:
Operating conditions:
6661101_202002
24V DC, +/-10%
3 W
500 m
(databus)
IP30
-20 to +60°C,
85% rel. hum.,
non-condensing
ELECTRICAL CONNECTION:
Databus Power supply