Function Groups

Factory settings are highlighted grey.
9.1

Help Texts (running text)

9.2

Signal inputs

Page 10
Help Text menu
Select Help Text
ON
- a running text that has
started can be aborted with
any programming key
OFF
Select language for Help Text
English
Deutsch (German)
Menu Input Signal
Select measuring range
Meas. range 0 ... 10 V
Meas. range 2 ... 10 V
Meas. range -10 ... +10 V
Meas. range 0 ... 20 mA
Meas. range 4 ... 20 mA
Select lower measuring range
limit
Input range depends on meas.
range [V / mA]
Select upper measuring range
limit
Input range depends on meas.
range [V / mA]
Select decimal point
(optical function only)
0
0.0
0.00
0.000
0.0000
Select input low value
Input range depends on meas.
range [V / mA]
Select display low value for
INP.LO.
Input range
-199999 ... +999999 and DP
Select input high value
Input range depends on meas.
range [V / mA]
Select display high value for
INP.HI.
Input range
-199999 ... +999999 and DP
Select Input Filter
The Filter function shows how
many measurement cycles are
used to determine the moving
average.
Input range 1 ... 99 [cycles]
- with a value of 1 the filter
function is switched off
Select Start Delay after Power
On
(limit monitoring is processed
only after the programmed
time has expired)
Input range 0.0 ... 99.9 [sec]
Select local mains frequency
Mains frequency 50 Hz
Mains frequency 60 Hz
Input range depends on measuring range:
0 ... 10 V = -0.500 ... 10.500 [V]
2 ... 10 V = 1.500 ... 10.500 [V]
-10 ... +10 V = -10.500 ... +10.500 [V]
0 ... 20 mA = -0.500 ... 21.000 [mA]
4 ... 20 mA = 3.000 ... 21.000 [mA]
The functions LO.LIM and HI.LIM limit the
editable range.
The value for HI.LIM must always be
greater than the value for LO.LIM.