Defrost Stopping Temperature Parameter
For evaporator sensor selection parameter
while defrost operation, if evaporator temperature reaches to temperature that defined at
this parameter in a shorter time than
Defrost at Power On Selection and Defrost Delay Parameter
( Default =
) MODBUS ADDRESS:40014
It can be adjust from 0 to 99 minutes. When tihs parameter is 0, if decrement button is
pressed,
is observed. In this condition system goes through a defrost cycle at the
end of the defrost repeat cycle time
0 and 99, then system goes through a defrost cycle at the end of the this parameter time
after power on.
Display Status During Defrost Parameter
MODDBUS ADRESS:40015
The cabinet temperature value is displayed during defrost.
Cabinet temperature value at the start of the defrost is displayed during defrost.
Temperature set value is displayed during defrost.
is displayed to indicate the defrost is in progress.
Displaying Current Temperature Delay After Defrost Parameter
MODDBUS ADRESS:40016
This parameter defines the delay for displaying current temperature being active after
defrost.
It can be adjusted from 0 to 255 minutes.
Dripping Time Parameter
This parameter defines for dripping time after defrost.
It
can be adjusted from 0 to 15 minutes.
Temperature Alarm Delay After Dripping Parameter
ADDRESS:40018
This parameter defines the delay for temperature alarm being active after dripping time
completion. It can be adjusted from 0 to 15 minutes.
Compressor Start Delay at Power On Parameter ( Default = 0 )
MODBUS ADDRESS:40019
When power is first applied to the device,This time delay must be expired for activation of
compressor. It can be adjusted from 0 to 20 minutes.
Compressor Start-Start Delay Parameter ( Default = 0 )
MODBUS ADDRESS:40020
This time delay must be expired between two activation of the compressor.
It can be adjusted from 0 to 20 minutes.
Minimum Compressor OFF Time Parameter ( Default = 0 )
When compressor is inactive, this time delay must be expired for activation of the
compressor. It can be adjusted from 0 to 20 minutes.
Minimum Compressor ON Time Parameter ( Default = 0 )
When compressor is active, this time delay must be expired for deactivation of the
compressor. It can be adjusted from 0 to 20 minutes.
Cabinet Probe Defect Parameter ( Default = 0 ) MODBUS ADDRESS:40023
Compressor is OFF in case of cabinet probe defect.
Compressor is ON in case of cabinet probe defect.
Compressor operates periodically according to
in case of cabinet probe defect.
Compressor Active Time in Case of Cabinet Probe Defect Parameter (Default = 0)
MODBUS ADDRESS:40024
If cabinet probe defect parameter
It canbe adjusted from
Compressor İnactive Time in Case of Cabinet Probe Defect Parameter
( Default = 0 ) MODBUS ADDRESS:40025
If cabinet probe defect parameter
It canbe adjusted from
(Default = 2°C) MODBUS ADDRESS:40013
is 1 (evaporator sensor is active),
parameter, then defrost operation stops.
after power on.If this parameter value is between
( Default = 3 )
(Default = 2) MODBUS ADDRESS:40017
is 2, then this parameter is observed.
to 99 minutes.
is 2, then this parameter is observed.
to 99 minutes.
( Default = 0 )
(Default = 0) MODBUS
MODBUS ADDREDS:40021
MODBUS ADRES:40022
and
time periods
10