ETA SYSTEMS - UNINTERRUPTIBLE POWER MANAGER
Mechanical Data
VA Rating
Dimensions
H x W x D
350 VA
in.
6.6 x 5.5 x 17.5
350 VA
mm.
168 x 140 x 445
500 VA
in.
8.0 x 5.8 x 17.5
500 VA
mm.
203 x 147 x 445
800 VA
in.
8.0 x 5.8 x 17.5
800 VA
mm.
203 x 147 x 445
1100 VA
in.
9.0 x 8.3 x 19.5
1100 VA
mm.
229 x 211 x 495
1440 VA
in.
9.0 x 8.3 x 19.5
1440 VA
mm.
229 x 211 x 495
Environmental Data
Factor
Operating
o
o
Temperature
0-40
C (32-104
F)
Humidity
5 – 90% non-condensing
Altitude
3,000m (10,000 ft.) max.
Battery and Charger
VA Rating
350 VA
DC Voltage
24V
Battery Type
12V, 4.5AH
Quantity
2
Recharge Time
4 hours
Noise Rejection and Isolation
With unit under power and an ANSI/IEEE C62.41 Category A impulse applied either normal mode
or common mode at the input, the noise output voltage will be less than 10V normal mode and
0.5 volts common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM)
Shipping Weight
North American (lbs.)
31
37
43
65
69
Shipment/Storage
o
o
o
-20
-+60o C (-4
- +140
5 – 90% non-condensing
12,000m (40,000 ft.) max.
500 VA
800 VA
1100 VA
24V
24V
24V
12V, 4.5AH
12V, 7AH
12V, 11AH
2
2
4 hours
4 hours
4 hours
94
ShippingWeight
International (kg.)
17
17
20
29
29
F)
1440 VA
24V
12V, 7AH
2
4
4 hours