Programmable value: 0...50%Pn
Pn
= 3-phase active rated power = 3-phase rated voltage Un x rated current In x√3
Un: 400V
In: 1A or 5A
= 400V x5A x √3= 3464W or 400V x1A x√3= 692,8W
Pn
1.7 RS485 communication
(where provided)
According to the models, this meter can be without communication or equipped with
RS485 ModBus RTU/TCP
Address number: 1...255
Parity bit: none – even – odd
Waiting time before answer: 3...100ms
Transmission speed: 4800 – 9600 – 19200 – 38400 bit/s
ModBus message word format
1
Just for 32-bit quantities
1.8 Pulse output
(max.27 50m )
Quantity that can be coupled: active or reactive energy
Pulse weight: 1pulse/10Wh(varh) – 100Wh(varh) – 1kWh(kvarh) - 10kWh(kvarh) -
100kWh(kvarh) – 1MWh(Mvarh) - 10MWh(Mvarh)
Width of the pulse: 50 – 100 – 200 – 300 – 400 – 500ms
1.9 Harmonic Analysis
Display mode: up to the 9
th
harmonic or up to the 25
Password = 2001
Level 2
2.1 Full scale current and external VT ratio
Vt
=External primary/secondary VT ratio
Ct =
Full scale current value
Selectable values: 1000 – 3000 – 5000A
By modifying the full scale current value and/or external VT ratio, the energy KWH
meters are automatically reset
Password = 3002
Level 3
3.0 Communication protocols
02/18 E04 10783304 WEB E cod.MF96421SR
1
: Big Endian – Little Endian – Swap
th
harmonic.
(ex. TV 600/100V Vt = 6)
(See point 3 page 21)
Phase sequence diagnostic
In the software of the device we have added a specific functionality to detect and correct
many problems concerning voltage and / or current connection.
This function can be activated through password and allows to display and modify the
connection sequence provided that the following conditions are respected:
1) The neutral wire (in a 4-wire network) is connected to the right terminal
ber 1)
2) No crossings between cables connected to CT's
nals 1 and 3 - are connected some way both to CT1 and CT2)
3) The power factor is between 1 and 0,5 - Inductive load - for each phase.
See www.imeitaly.com "TECHNICAL SUPPORT"
Optional modules
(See page 20)
By connecting some optional modules, it is possible to have further communication outputs
(see table)
Nemo 96 HDLe
Module
IF96001
IF96002
IF96007A
IF96009
MF96421SR
IF96012
IF96013
IF96014
IF96015
Nemo 96 HDLe
Rogowski
(normally num-
(e.g. avoid that on phase 1 of the meter-termi-
.
.
Output 1
Output 2
Output 3
Pulse
RS485
Pulse
RS485
RS485
Pulse
RS485
RS232
Pulse
RS485
PROFIBUS
Pulse
RS485
LonWorks
Pulse
RS485
Memory + RS485
Pulse
RS485
M-Bus
Pulse
RS485
BACNET
Pulse
RS485
ETHERNET
5