G
®
THERMASREG
Mechanical temperature controller ⁄ wet room temperature controller THERMASREG
working without external voltage. It is used for moni toring and to control temperatures in heat generation plants, in heating, ventilation and air
conditioning systems, for ventilation, cooling and climate control in halls, cold storage rooms, greenhouses, nurseries, stables, breeding rooms, as
industrial room thermostat or surface-mounted thermostat in industrial applications as well as in wet room and outdoor areas.
TECHNICAL DATA:
Switching capacity: ................. 24 ... 250 V AC + 10 %, 16 A, cos ϕ = 1.0
(Contact load)
Contact: ............................... dustproof switch block unit as potential-free
Enclosure: ............................. plastic, material polyamide, 30 % glass-globe-reinforced,
Enclosure dimensions: ............. 108 x 70 x 73.5 mm (Thor II)
Cable gland: ........................... M 20 x 1.5 ; including strain relief
Enclosure temperatur: ............. - 35 °C ...+ 65 °C
Design principle: ..................... torsion meter with liquid filling
Capillary: .............................. copper
Tolerance: ............................. T
Electrical connection: .............. 0.14 - 2.5 mm
Protection class: .................... I (according to EN 60 730)
Protection type: ..................... IP 65 (according to EN 60 529)
Standards: ............................ CE conformity, EMC directive 2004 ⁄ 108 ⁄ EC,
FUNCTION:
Heating: ................................ The preset setpoint (scale value) is equivalent to the switch-off value of the heating.
Cooling: ................................ The preset setpoint (scale value) is equivalent to the switch-on value of the cooling.
Type ⁄ WG2
TR 22
T R - 2 2
TR 22 U
T R - 2 2 U
TR 22
(For further information see table!)
24 ... 250 V AC + 10 %, 1.5 A, cos ϕ = 0.6
at 24 V AC min. 150 mA
single-pole changeover contact
with quick-locking screws,
colour pure white (similar RAL 9010)
± 3 K; T
± 3 K
min
max
2
via terminal screws
low-voltage directive 2006 ⁄ 95 ⁄ EC
The switch-on value is lower by the amount of operating difference.
Contact 2 - 3 breaks when temperature rises to the preset value.
The switch-off value is lower by the amount of operating difference.
Contact 1 - 2 closes when temperature rises to the preset value.
Temperature
Thermal Operating
Range
Difference (fixed) ca.
– 35 ...+ 35 °C
– 35 ...+ 35 °C
®
TR 22 with switching output (one-step) and copper capillary,
Max. Capillary
Temperature
3 K (± 1 K)
+ 60 °C
3 K (± 1 K)
+ 60 °C
Connecting diagram
2
3
1
Item No.
TR
(External setting)
1102- 1050-1100- 100
TW (Internal setting)
1102- 1050-2100- 100