Notes to Installation Technician
Verify the manifold pressure by using a 3/8" flared T-junction at the location marked in the
diagram below. Then, using a digital manometer, verify that the pressure before the orifice is
7 W.C. (1.74 kPa). Also verify that the orifice spud has the 3.9 mm stamp. This will allow you to
verify that the input rating of the fireplace is correct.
Installing at Altitude
Installations at elevations above 2,000 ft (609.6 m) may require adjustment. Contact
Real Flame Customer Service at 1-800-654-1704 for further information.
NOTE: The normal manifold pressure for this converted appliance is 7" water column.
NOTE: The maximum inlet gas pressure for this unit is 10.5 in W.C. (2.61 kPa).
The minimum inlet gas pressure for this unit is 3.5 in W.C. (0.87 kPa).
PRE-USE INSTRUCTIONS
10
To Manometer