Reversible unit - Heat pump technical specifications
ILD - ILDC - ILDH
Cooling capacity ①
Power input
EER Efficiency ②
Seasonal efficiency ESEER
Lw / Lp ③ (High Perf. - HP)
Lw / Lp ③ (Low Noise version - LN)
Lw / Lp ③ (Xtra Low Noise version - XLN)
Heating capacity ①
Power input
Performances COP ②
Compressor
Starting mode
Quantity
Capacity control
Refrigerant oil type
Oil volume
Refrig. circuit number
Refrigerant fluid (GWP)
Refrigerant load
Electric supply
Unit protection index
Circuit control voltage
Evaporator
Water content
Chilled water outlet min. / max.
Hot water outlet min. / max.
Minimum water flow
Maximum water flow
Water connections
Maximum pressure (water side)
Air cooled condenser
Fan ∅
Number x Motor rated power
High Performance series - HP
Number x Motor rated power
Low Noise series - LN
High Performance air flow - HP
Low Noise air flow - LN - XLN
Mini water content (ILD-ILDC)
Water tank content model H
Expansion vessel model C & H
Standard pump
Height without mounts
Standard series length
C series length
H series length
Depth
Std range weight without charge
C range weight without charge
H range weight without charge
Storage temperature
➀ Capacity for HIGH PERFORMANCE version based on:
a/ COOLING: +12°C/+7°C and condenser air inlet temperature +35°C
b/ HEATING hot water outlet +45°C and external air +7°C dry bulb 86%RH
➁ Gross EER or COP values
➂ Overall capacity level Lw, overall pressure level Lp at 10 metres, free field, in accordance with the ISO 3744 standard
➃ Depending on selection
(1) Capacity of the installation as a function of the expansion vessel mounted on the
unit. The auxiliary tank is already taken into account. In the case where the
installation capacity is higher, an expansion vessel must be added on the installation
corresponding to the surplus capacity.
350V
400V
500V
kW
92.8
105.2
128.1
kW
31.4
35.2
44.4
2.96
2.98
2.88
3.70
3.84
3.27
dB(A)
89/57
90/58
dB(A)
83/51
dB(A)
-
-
-
kW
95.0
108.8
132.6
kW
31.4
36.0
43.1
3.03
3.02
3.07
2
2
2
100-57-
100-63-
%
100-50-0
43-0
37-0
l
8.8
9.8
11.2
1
13.0
kg
21
24
+13.0
ph/Hz/V
ph/Hz/V
l
8.68
9.88
10.66
°C
-10 / +18
°C
m
3
/h
11.7
13.3
17.3
m
3
/h
30.7
34.6
41.9
∅
Male G 2"1/2
bar
mm
nb x kW
2x1.7
2x1.7
2x1.8
nb x kW
2x1.2
2x1.2
2x1.2
m
3
/h
44000
42000
41000
m
3
/h
32000
29000
30500
l
220
213
357
l
l
n°
mm
2117
mm
2190
mm
2190
mm
2190
mm
2129
kg
1096
1195
1283
kg
1194
1292
1355
kg
1257
1356
1418
°C
47
540V
600V
700V
702V
139.9
155.3
163.1
183,4
46.1
52.5
59.5
61,5
3.03
2.96
2.74
2,98
3.97
3.95
3.63
3.83
91/59
85/53
-
-
-
81/49
147.1
164.0
181.5
191,1
47.7
53.0
57.1
63,2
3.08
3.09
3.12
3.02
Hermetic SCROLL 2900 rpm
Direct in series
4
4
4
4
100-78-
100-78-
72-55-
100-75-
100-78-
71-57-
50-45-
50-25-0
50-22-0
50-43-
28-22-0
28-21-0
Polyolester POE 3MAF (32cst)
14.8
16.6
17.6
17.6
2
R410A (1890)
18.0
18.2
18.0
+18.0
+19.2
+18.0
3~50Hz 400V (+6%/-10%) + Earth
IP 44
1~50Hz 230V (+6%/-10%) - transformer mounted
Brazed plates type exchanger
12.48
15.42
15.42
15.8
+30 / +50
18.1
20.8
20.8
22,1
45.9
50.7
50.7
63,2
Flange DN80
ILD 10 bars / ILDC-ILDH 4 bars
Finned heat exchanger
800
2x1.7
2x1.7
2x1.7
4x2.24
2x1.1
2x1.1
2x1.1
4x1.48
44000
44000
44000
35000
35000
35000
164
207
203
213
250
18
➃
2117
2740
2740
2740
2129
1570
1706
1878
2270
1675
1804
1976
2550
1748
1868
2040
2680
+ 50°C
(2) The water temperatures mentioned are the temperatures which can be reached
when the unit is stopped
800V
900V
1000V
1100V
201,8
239,8
257,9
278,8
69,8
83,0
91,9
101,5
2,89
2,89
2,81
2,75
3.81
3.75
3.77
3.63
92/60
87/55
82/50
81/49
81/49
83/51
213,5
247,9
265,2
285,7
71,5
82,7
89,9
97,1
2.99
3.00
2.95
2.94
4
4
4
4
100-81-
100-80-
100-77-
100-83-
69-62.5-
70-60-
73-54-
66-55-
50-37.5-
50-40-
50-45-
33-16-0
31-19-0
30-20-0
27-33-0
21.8
20.8
22.2
26.2
36.0
+37.0
15.8
18
20.4
20.4
-12 / +18
24,4
29,3
31,6
34
69,5
77
77
77
Flange DN100
4x2.24
4x2.24
4x2.24
4x2.24
4x1.48
4x1.48
4x1.48
4x1.48
84300
63180
212
213
290
364
500
34
2080 (+205 XLN)
3698
3698
3698
2200
2320
2365
2445
2505
2600
2645
2725
2825
2730
2775
2855
2955