Commissioning

4
Commissioning
4.1

DIP switch settings

Switch
DIP 1
NVF sensor
(NVF-104/34-PF)
DIP 2
KVF sensor
(KVF-104-PF) or
SLU sensor
(SLU-103-**)
DIP 3
Acoustic alarm
DIP 4
Relay setting
DIP 5
DIP 4
Relay setting
DIP 5
DIP 4
Relay setting
DIP 5
DIP 4
Relay setting
DIP 5
DIP 6
Repeat alarm
setting in
24 hours
DIP 7
Reset key
(ALARM RESET
activation)
DIP 8
Not in use.
Description
ON
connected
OFF
not connected
ON
connected
OFF
not connected
ON
Acoustic alarm switched on.
OFF
Acoustic alarm switched off.
ON
Relays 1 and 2 switch in all alarm states. If an alarm event is no
longer pending, relay 1 switches back automatically AND relay 2
ON
remains unchanged until the alarm has been acknowledged by
actuating "ALARM RESET". This shows therefore that an alarm was
present.
ON
Relays 1 and 2 switch in alarm states. After 3 minutes, relay 2
switches back (even if an alarm state is pending). If the alarm state
OFF
disappears, relay 1 and/or relay 2 switches again. (If "ALARM
RESET" is actuated, the relays switch again)
OFF
Relay 1 switches with alarm state at NVF sensor; relay 2 switches
with alarm state at KVF sensor or SLU sensor. If the alarm state
ON
disappears, relays 1 and/or 2 switch again (if "ALARM RESET" is
actuated, the relays switch again).
OFF
Relays 1 and 2 switch in alarm states irrespective of which sensor.
If the alarm state disappears, relays 1 and/or 2 switch again
OFF
(if "ALARM RESET" is actuated, the relays switch again).
ON
Repeat alarm setting switched on. This also applies to the function
of relays 1 and 2.
OFF
Repeat alarm setting switched off
ON
ALARM RESET is active. The acoustic alarm and the alarm relay
are reset.
OFF
ALARM RESET is deactivated. The acoustic alarm and the alarm
relay are not reset.
EN
EN - 19