"POWER POINT" (AP735USA - SW 1.07)
USER MANUAL / MANUEL D'INSTRUCTIONS
M) DISPLAYED FAULTS
The following table describes faults which may occur during a charging process.
This information is very useful to release the charger lock and it has to be given to the service personnel in
case their action in required.
FAULT
POWER FAILURE
OPERATION OF
OVERLOAD CUTOUT ON
TRANSFORMER
OPERATION OF SAFETY
TIMER
FAILURE OF RECTIFIER
BRIDGE
FAILURE OF ON-OFF
RELAY/CONTACTOR
MAXIMUM VOLTAGE
MINIMUM VOLTAGE
(from rel. 1.06)
N) GUARANTEE
-
The charger is guaranteed for 24 months from the date of installation.
The guarantee covers all proven defects in components, assembly and construction.
-
Any incorrect installation or use of the machine NULLIFIES the guarantee.
-
Any unauthorised tampering NULLIFIES the guarantee.
-
-
In case of difficulties please contact the LOCAL DEALER or PBM Srl
P.B.M. S.r.l.
via Barella, Z.I. - VIGNOLA ( MO ) ITALIA
Tel. + 39 059 770 53 11 - Fax + 39 059 770 53 00
http://www.gruppopbm.it e-mail : pbm@gruppopbm.it
Alarms are reset by disconnecting the battery.
DESCRIPTION
There is no mains power supply.
On power-fail restart the charging
process is regularly resumed.
Transformer may be overheated.
Charging will not continue until
the transformer has cooled down.
Check battery conditions.
Battery charger is not able to
charge battery within the set time
limits.
Check battery conditions and
mains selection on transformer.
Battery charger can not deliver
current for more than 2 minutes.
Check rectifier bridge.
Current is delivered even if
charge is stopped. Disconnect
from mains and check relay and
power circuits.
Voltage at battery terminals
exceeds 2.90 V/cell. Check
battery rated voltage or jumper
position in Swbat.
Voltage at battery terminals
before the charging process is
lower than 1.70V/cell. Check
battery rated voltage or jumper
position in Swbat.
pag. 11
LED
Red LED
blinking
Red LED
blinking
Red LED
constant
Red LED
constant
Red LED
constant
Red LED
constant
Red LED
constant
file : POWER Point _USA+CAN_ Wa-WOWa_rev16.doc
Revision no. 16 dd. 21/04/2008
DISPLAY