Connecting the EIM to the Lighting Panel
10. In the menu tree on the left side of the screen, expand
the Operating Settings folder.
1.
Select the Port 1 folder within the Operating Settings
folder.
2.
In the Operating Settings screen, set the following
parameters:
Operation Mode: TCP Server Mode
TCP alive check time: 1 minute
Inactivity time: 0
Max Connection: 4
Local TCP port: 10001 recommended (or other port
specified by the IT administrator)
Other fields not identified should be left at default
settings shown
3.
Select the Submit button.
4.
In the Operating Settings OK screen, select the Save/
Restart button.
11. Once the Save/Restart OK screen appears, close the
web browser. Configuration is complete.
4
Ethernet Interface Module
Remember to reset your computer's network TCP/IP
settings to their original settings. If you need to reconnect
through the web server pages, you will need to make
certain that your computer is configured to communicate
on the same subnet as the EIM device. Instead of typing in
the default address in the browser address, you will need to
use the unit's assigned IP Address.
Connecting the EIM to the Lighting Panel
After configuration is complete, it will be necessary to
connect the device to the lighting control panel using the
following steps:
1.
Connect the supplied phone style communications
cable to the female 9 pin adapter head provided.
2.
Connect the 9 pin adapter head to the Ethernet
Interface Module's serial port.
3.
Connect the other end of the phone style
communications cable to the RJ11 style COM port on
the Lighting Control Panel. (on some controllers there
are two RJ11 style connectors. Please connect the
cable to connector labeled RS-232.)
4.
Connect one end of the Ethernet cable to the Ethernet
Interface Module RJ45 port and the other end of the
cable to the Ethernet network.
12. Plug in the power adapter supplied with the device.
The Ethernet Interface Module (EIM)
can be connected to any controller in the network.
Lighting Control Software
NET
POWER
STATUS
RESET
50-022180-02
C
PCI 2005
LED4
LED5
LED1
LED2
LED3
54-022180-
RSC POWER
RSC LINK
CAN-TX
CAN-RX
J7
TMS
J1
PCI-NET
TDO
TDI
TCK
J2
VCC
GND
J3
DIGITA
J4
RS-232
J5
PCI-NET
J6
PCI-NET
JTAG
TB1
Ethernet Interface
J8
IND1
SR1
C29
Module (EIM)
J9
LCD
ADJ
J10
D3
D4
D5
D6
C43
REM
PWR
ANALOGS
ICD LINK
TB2
RS-485 Network
TB3
LED6
LSC
TEST
to Other Lighting
ON +24 OFF LSO
CH
17
ON +24 OFF LSO
CH
18
ON +24 OFF LSO
CH
19
ON +24 OFF LSO
CH
20
ON +24 OFF LSO
CH
21
ON +24 OFF LSO
CH
22
ON +24 OFF LSO
CH
23
ON +24 OFF LSO
CH
24
ON +24 OFF LSO
CH
25
ON +24 OFF LSO
CH
26
ON +24 OFF LSO
CH
27
ON +24 OFF LSO
CH
28
ON +24 OFF LSO
CH
29
ON +24 OFF LSO
CH
30
ON +24 OFF LSO
CH
31
ON +24 OFF LSO
CH
32
TP1
CH
1
CH
2
CH
3
CH
4
CH
5
CH
6
CH
7
CH
8
CH
9
CH
10
CH
11
CH
12
CH
13
CH
14
CH
15
CH
16
Control Panels
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
ON +24 OFF LSO
RS-232 Phone Style
Cable with Adapter
Cable Head
HUB
Building LAN
AC Adapter