MCP
Catalog
Number
PDG23M0025MLAJ
PDG23M0050MLAJ
PDG23M0070MLAJ
PDG23M0100MLAJ
6
EATON
IL012326EN
TABLE 3-2: SPECIAL APPLICATION MCP TRIP SETTINGS
Cam
Setting
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H
Motor FLA ranges are typical. The corresponding trip
¹
setting is 13 times the FLA value shown. The _ 20%
trip tolerances can affect trip response and require
increase in cam setting per para 3-2.
For dc applications, actual trip levels may exceed the
values shown by as much as 100%. Actual dc trip
²
value are application dependent.
Settings above 130 amps are for special applications.
N.E.C Article 430-110(a) requires the ampere rating
³
of the disconnecting means to be not less than 115%
of the motor full ampere rating.
Continuous
Ampere
Rating
25A
50A
70A
100A
MCP
Trip
Setting
²
40
43
46
49
52
55
58
60
81
87
93
98
103
109
115
120
114
122
130
139
145
153
160
168
163
174
185
196
207
218
229
240
+