7. Test run
The speed of the outdoor unit fan is controlled in order to control the performance of the unit. Depending on the ambient air, the fan will rotate at a slow speed and will keep
not a problem.
1
Note: If an error is displayed on the remote controller, see the table below.
LCD
Description of malfunction
P1
Intake sensor error
P2
Pipe sensor error (liquid pipe)
P4
disconnected (CN4F)
P5
P6
operation
P8
Pipe temperature error
See the table below for the details of the LED display (LED 1, 2, and 3) on the indoor controller board.
LED1 (microcomputer power supply)
LED2 (remote controller power supply)
Note:
If the unit is operated continuously during a test run, the unit stops after 2 hours.
[Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
received)
code in the following table (i.e., n=5 for "P5")
[Output pattern B]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
received)
LCD
P9
PA
PB (Pb)
PL
FB
(* indicates an
alphanumeric
character
excluding FB.)
Indicates whether control power is supplied. Make sure that this LED is always lit.
Indicates whether power is supplied to the wired remote controller. The LED is lit only for the indoor unit that is connected
to the outdoor unit that has an address of 0.
Indicates whether the indoor and outdoor units are communicating. Make sure that this LED is always blinking.
Beep
Beep
Beep
Beep
1
st
2
nd
3
rd
n
th
On
On
On
On
0.5 sec.
0.5 sec.
0.5 sec.
0.5 sec.
Beep
Beep
1
st
2
nd
On
On
On
Approx. 3 sec.
0.5 sec.
0.5 sec.
Description of malfunction
Pipe sensor error (dual-wall pipe)
Leakage error (refrigerant system)
Indoor unit fan motor error
Refrigerant circuit abnormal
Indoor controller board error
Outdoor unit malfunction
Refer to the wiring diagram for the
outdoor unit.
Beep
Beep
1
st
2
nd
· · · Repeated
Off
On
On
Approx. 2.5 sec.
0.5 sec.
0.5 sec.
the check code in the following table
Beep
Beep
3
rd
n
th
On
On
Off
0.5 sec.
0.5 sec.
Approx. 2.5 sec.
LCD
Description of malfunction
Communication error between the
E0 – E5
remote controller and the indoor
unit
Communication error between the
E6 – EF
indoor unit and the outdoor unit
Beep
Beep
1
st
2
nd
· · · Repeated
On
On
On
Approx. 3 sec.
0.5 sec.
0.5 sec.
the check code in the following table