Overload
Electronic shutdown until overload or short
PM863 & PM865
circuit removed (under mains power only)
Overload
Fuse Protection
PM861 & PM862
Standby battery
Battery type
2 x12 Vdc Valve Regulated Lead Acid
Battery capacity
See below under Mechanical specifications.
Local Indicators
Mains LED (Green)
Mains present
Fault LED (Yellow)
Fault present: Output fuse fail or battery fuse
fail (requires load and battery to be
connected), loss of mains, output short
circuit or low output voltage.
See Diagnostic Table.
Charge LED (Orange)
Battery Charging
Diagnostic Table
M
F
C
AINS
AULT
HARGE
LED
LED
(
)
(
)
(
GREEN
YELLOW
ORANGE
ON
OFF
OFF
ON
OFF
1s ON,
ON
1s OFF
or OFF
0.1s ON,
OFF
OFF
3s OFF
OFF
OFF
OFF
Signaling Outputs
Tamper
3 A, 125 Vdc N/C volt-free contacts.
Contact closed when the lid is closed and
unit securely mounted (TAMPER INACTIVE
condition).
0.1 A @ 60 Vdc N/O volt-free contacts.
GEN Fault (general)
Open when battery disconnected, output
fuse fail, battery fuse fail, and output short
circuit or low output voltage.
0.1 A @ 60 Vdc N/O volt-free contacts.
EPS Fault (mains)
Open when loss of mains for more than 8s.
Mechanical
Model
PM861, PM862
Enclosure dimensions
330 x 275 x 80
w x h x d (mm) [external]
2 x BS127N
Battery capacity
(7.2 Ah)
Weight (kg) excluding
2.98
battery
Environmental
−10 to +40°C (operating) 95% RH non-condensing
Temperature
−20 to +80°C (storage)
Connections
+O/P
+ve voltage O/P to load equipment
−ve voltage O/P to load equipment
-O/P
+BATT
Red lead to standby battery 1 positive
P/N PAK200535 • REV D • ISS 21MAR19
LED
S
TATUS
)
NORMAL - battery fully charged
ON
NORMAL - battery charging
ON
FAULT - see Signaling Outputs
FAULT - Mains Loss
PSU operating on battery standby
FAULT - No Output
Mains and Battery loss
PM863, PM865
330 x 275 x 80
2 x BS127N
(7.2 Ah)
3.30
-BATT
Black lead to standby battery 2 negative
GEN Fault
Volt-free contacts for general faults
EPS Fault
Volt-free contacts for loss of mains indication
Specifications subject to change without notice.
Regulatory information
Manufacturer
PLACED ON THE MARKET BY:
UTC Fire & Security Americas Corporation, Inc.
3211 Progress Drive, Lincolnton, NC, 28092,
USA
AUTHORIZED EU REPRESENTATIVE:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Product warnings
THESE PRODUCTS ARE INTENDED FOR
and disclaimers
SALE TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS. UTC FIRE & SECURITY
CANNOT PROVIDE ANY ASSURANCE THAT
ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY "AUTHORIZED
DEALER" OR "AUTHORIZED RESELLER", IS
PROPERLY TRAINED OR EXPERIENCED TO
CORRECTLY INSTALL FIRE AND SECURITY
RELATED PRODUCTS.
For more information on warranty disclaimers and
product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/
or scan the QR code.
Certification
European Union
UTC Fire & Security hereby declares that this
directives
device is in compliance with the applicable
requirements and provisions of the Directive
2014/30/EU and/or 2014/35/EU. For more
information see www.utcfireandsecurity.com or
www.interlogix.com.
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info
This product may contain a battery that cannot be
disposed of as unsorted municipal waste in the
European Union. See the product documentation
for specific battery information. The battery is
marked with this symbol, which may include
lettering to indicate cadmium (Cd), lead (Pb), or
mercury (Hg). For proper recycling return the
battery to your supplier or to a designated
collection point. For more information see
www.recyclethis.info
Contact information
For contact information visit our Web site:
www.utcfireandsecurity.com
3 / 16