TX700S-P3WV01
EN
Quick Start Guide
HMI – TX700S-P3WV01
Other documents
The following additional documents are available online at
Data sheet
Instructions for use for TX series
EU declaration of conformity (current version)
For your safety
Intended use
The IIoT edge controllers of the TX700 family are used to control, operate and
monitor machine processes.
The devices may only be used as described in these instructions.
Any other usage shall be considered improper and Turck shall not be held liable
for any resulting damage.
General safety instructions
The device may only be assembled, installed, operated, parameterized and
maintained by professionally-trained personnel.
The device only meets the EMC requirements for industrial areas and is not
suitable for use in residential areas.
The devices may only be used in accordance with applicable national and
international regulations, standards and laws.
Do not open the devices under voltage.
Note on explosion protection (USA and Canada only)
The devices are approved for operation in hazardous areas only in the USA
and Canada and do not have ATEX approval.
The devices are suitable for the use in Class 1, Division 2, groups A, B, C and D
hazardous locations or for the use in non-hazardous locations.
Product description
Device overview
See fig. 1
Functions and operating modes
The IIoT edge controllers combine control, operation and monitoring by a
CODESYS V3 PLC with web visualization to a complete control unit. The
CODESYS V3 control of the TX700 has the functions PROFINET controller,
EtherNet/IP scanner and Modbus TCP as well as Modbus RTU master. Addition-
ally the devices of the TX700 family can be used as Modbus TCP and Modbus
RTU slave.
The devices were designed as CODESYS V3 PLC and IIoT edge controller for DIN
rail mounting.
Additional functions
Ethernet TCP/IP or UDP/IP communication
OPC-UA server and client, MQTT
Serial communication via RS232, RS485 and RS422
Installing
Hook the device into the top-hat rail from below and tilt it upwards until the
upper snap-in hook engages on the DIN rail.
Do not cover the ventilation slits in the device.
Connecting
DANGER
Ignitable atmosphere
Explosion by ignitable sparks
Do not disconnect the device in an ignitable atmosphere when energized.
Disconnect the device from the power supply before replacing or connect-
ing modules.
Connectors and slots
See fig. 3
Connector/slot
Function
1
Serial interface
2
Power supply
3
Ethernet port 1 (10/100 Mbit)
4
Ethernet port 0 (10/100 Mbit)
5
USB port , V2.0, max. 500 mA (for maintenance only)
6
Expansion slot for plug-in modules
7
SD card slot
DANGER
Unsuitable wiring
Loss of suitability for Class 1, Division 2
Connect the power supply, the inputs and outputs (I/O) according to
www.turck.com
Class I, Division 2 and according to the specifications of the respective com-
petent authority. For the USA, suitability according to Article 501.10 (B) of
the National Electrical Code, NFPA 70 and for Canada, suitability according
to Section 18-1J2 of the Canadian Electrical Code.
NOTE
Devices of protection class III according to EN 61140 or Class 2 according to UL
standards: All connections are SELV connections.
Power supply
Connect the device to the voltage supply according to fig. 4 and 5.
DANGER
Wrong selection of power supply
Danger to life due to overvoltage and electric shock!
Operate the device only on SELV voltage sources according to European
standard or on Class 2 voltage sources according to UL standard.
Grounding the device
The minimum conductor cross-section for the ground connection is 1.5 mm².
Ground the housing via the grounding screw on the back of the housing.
Connect terminal 3 on the power supply terminal block to ground.
Serial interface
See fig. 5
Pin
1
2
3
4
5
6
7
8
NOTE
When used as RS485 interface, pins 1 and 2 as well as pins 3 and 4 must be
connected externally.
Operating
DANGER
Changing components
Explosion hazard – Suitability for Class 1, Division 2 possibly impaired
When replacing components, make sure that the suitability of the device
for Class 1, Division 2 is not affected.
Only use components that are suitable for use in Class 1, Division 2.
If necessary, take measures to restore suitability for Class 1, Division 2.
Maintenance
Clean the devices at regular intervals with a damp cloth.
Repair
The device must not be repaired by the user. The device must be decommis-
sioned if it is faulty. Observe our return acceptance conditions when returning
the device to Turck.
Disposal
The device is equipped with a rechargeable lithium battery, which is not user
replaceable.
For disposal, open the back of the device and remove the battery.
The device and the lithium battery must be disposed of properly in ac-
cordance with WEEE Directive 2012/19/EU and must not be included in
general household garbage.
RS232
RxD
TxD
CTS
RTS
+5 VDC output
GND
n. c.
Shield
© Hans Turck GmbH & Co. KG | 1000014083 2020-11 DE EN FR
RS422/RS485
CHB-
CHA-
CHB+
CHA+
+5 VDC output
GND
n. c.
Shield