TX700S-P3WV01
Technical Data/Certification Data
Device
Type
TX700S-P3WV01
Ident-No.
100009353
Power Supply
Supply voltage
24 VDC (10 to 32 VDC)
Current consumption
Max. 0.35 A at 24 VDC
System resources
CPU
ARM Cortex-A8, 1 GHz
Operating System
Linux RT
Flash
4 GB
RAM
512 MB
Real Time Clock, RTC Back-up,
Yes
Buzzer
Interface
Ethernet ports
2
Transmission rate
10/100 Mbps
USB ports 2
1 (Host V. 2.0, max. 500 mA)
Serial port
1
RS232, RS485, RS422, software configurable
Max. 2 serial ports using plug-in modules.
SD card
Yes
Expansion
1 slot for max. 2 plug-in modules
General Information
Operating temperature
-20 °C...+60 °C (vertical installation)
Plug-in modules and USB devices may limit the max.
temperature to +50 °C
Storage temperature
-20 °C...+70 °C
Relative humidity
5...85 % RH, non condensing
Protection class
IP20
Approvals
For installation in industrial environments:
- emission EN 61000-6-3, EN 61000-6-4
- immunity EN 61000-6-1, EN 61000-6-2
UL
cULus (UL File No. E484727)
- UL 61010-1, 3rd Edition and UL 61010-2-201, 1st Edition
- CAN/CSA C22.2 No. 61010-1, 3rd Edition and
CAN/CSA C22.2 No. 61010-2-201:14
cULus (UL File No. E484803)
Class I, Division 2, Groups A, B, C and D
© Hans Turck GmbH & Co. KG | 1000014083 2020-11 DE EN FR

Publicité

loading

Sommaire des Matières pour turck HMI-TX700S-P3WV01

  • Page 1 - CAN/CSA C22.2 No. 61010-1, 3rd Edition and CAN/CSA C22.2 No. 61010-2-201:14 cULus (UL File No. E484803) Class I, Division 2, Groups A, B, C and D © Hans Turck GmbH & Co. KG | 1000014083 2020-11 DE EN FR...
  • Page 2 Richtlinie 2012/19/EU entsorgt werden und gehören nicht in den Erweiterungssteckplatz für Plug-in-Module normalen Hausmüll. SD-Karten-Steckplatz Hans Turck GmbH & Co. KG | Witzlebenstraße 7, 45472 Mülheim an der Ruhr, Germany | Tel. +49 208 4952-0 | Fax +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 3 All connections are SELV connections. The devices may only be used as described in these instructions. Any other usage shall be considered improper and Turck shall not be held liable Power supply for any resulting damage.
  • Page 4 à la directive DEEE 2012/19/UE et ne doivent pas être Emplacement SD jetés avec les déchets ménagers normaux. Hans Turck GmbH & Co. KG | Witzlebenstraße 7, 45472 Mülheim an der Ruhr, Germany | Tel. +49 208 4952-0 | Fax +49 208 4952-264 | more@turck.com | www.turck.com...