Intended use
- Rack and pinion drive for electric opening and
closing of windows and flaps in the facade and
roof area
- Operating voltage 24 VDC
-
U
seable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
Safety notes
Operating voltage 24 VDC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the toothed rack!
- Use only in dry rooms
- Only for inside mounting
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Use option "-W" in case of outside mounting!
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed red safety slip!
Pressure load diagram
Maximum pressure load of the toothed rack is not
automatically identical with maximum pressure force
of the drive!
Loads from over 1000 N to 1500 N are only briefly
permissible (e.g. to throwing off snow or with wind
loads). These may arise up to a stroke of 800 mm.
1400
1200
1000
800
600
400
200
0
99.824.29 1.2/03/12
Permanent
Temporary
Stroke (mm)
Performance features
-
M
icroprocessor controlled electronics
-
A
djusting of stroke with PLP1 directly at the drive
- ndividually programmable
I
and PDA service tool)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
-
E
specially silent in ventilation operation
because of reduced motor speed
-
C
able entry interchangeable from the bottom
to the top
Scope of supply
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
Mounting informations
- Swivel radius of the drive must go free over entire
range of stroke. Otherwise, the toothed rack and
the suspension can be damaged
- Drives with a stroke of
ted „hung up at the bottom" (e.g. bracket UK)
- Eyebolt has to be adjusted so, that the drive is
disconnected with closed flap through it's inside
stop position damping. Brackets can be damaged
by to rigid adjustment!
- Technical clarification is required with D+H in case
of only tensile force applications of more than 500N
- A programming should be done before
installation, because the drives can only be
programmed individually connected
- ZA-TM drives may not be connected with a
coupling shaft (VW).
A combination with a slave unit (ZM) is permitted
ZA-TM
ZA-TM
VW
English
via Powerline (PLP1
800 mm
must not be moun-
ZA-TM
ZM
VW
5/16
ZA 35/85/105/155