SLAT AXS2 12V 5A Notice D'installation page 6

Masquer les pouces Voir aussi pour AXS2 12V 5A:

Publicité

Les langues disponibles

Les langues disponibles

Environmental specifications
-
Operating temperature: - 5° C to 50° C .
-
Storage temperature: - 25 to + 85° C .
-
Operating relative humidity: 20 to 95%.
Electrical input specifications
Single-phase voltage: 230V (195.5V-264.5V).
-
-
Frequency: 50-60Hz (from 45 to 65Hz).
-
Neutral systems: TT, TN, IT.
A D curve circuit breaker with easy access to be provided upstream.
-
Primary current @230V: 0.75A (12V 5A - 24V 2.5A); 1A (12V 10A).
-
Electrical output specifications
-
"floating" load output in relation to the ground.
-
Float voltage: 13.6V (12V 5A - 12V 10A); 27.2V (24V 2.5A).
Current limitation: 5A (12V 5A); 10A (12V 10A); 2.5A (24V 2.5A).
-
Alarm reports
2 dry contacts (open when faulty) 1A@24Vdc, 0.5A@120Vac :
-
Mains fault or rectifier fault.
o
Battery low voltage fault.
o
-
Indicated by a LED on the front panel.
Protection
Fuses on electronic board: see table « Motherboard fuses »
-
Mains:
Caution! This equipment is designed to be connected to the 230 Vac public distribution network, an
easily accessible isolating switch must therefore be installed outside of the cabinet.
Use a bipolar D curve circuit breaker to connect the power supply to the mains circuit. (2A for 12V 5A
and 24V 2.5A versions et 4A for 12V 10A version).
Batteries:
Caution! Install batteries after fixing the base of the cabinet to the wall (wall mounting with 4 points
with 4 screws
12V Version: connect battery using provided kit.
24V Version: connect 2 batteries in series using provided kit.
Connections
run cables through the inputs / outputs provided in the cabinet
-
cable section, mains, load, battery alarm reports:
-
0.3 to 2.5 mm² (12V 5A - 24V 2.5A)
o
0.3 to 6 mm² (12V 10A)
o
length to be stripped: 7mm
-
the bare parts of the cables must be crimped before being wired to the terminals of the product.
-
-
The conductors of mains and battery cables must be fixed with provided cable ties as close as possible to the
block terminals.
-
The mains cable must be fixed with the provided cable tie to the cabinet cable outlet (see below).
The other cables can be fixed with a cable tie (see below). 3 bases are factory assembled and are located on
-
the left of the cabinet cable outlet (top/middle/bottom). 7 locations are free to insert 7 clamp bases (supplied).
Installation
5 and 30mm min length)
6