Télécharger Imprimer la page

General; Fields Of Application; Technical Specifications; Standards - Approval - Socla BA 4760 Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour BA 4760:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 16
EN

General

Designed to protect drinking water supply networks against
the backflow of risk fluids up to category 4 according to NF
EN1717.
The device is designed to prevent any backflow of polluted
water into the drinking water supply network as a result
of back pressure or back siphonage when the pressure
upstream of the device is lower than the pressure downstream
of it.

Fields of application

For systems liable to generate pollution risks:
• Sanitary networks: hospitals, laboratories,
dialysis centres, water treatment.
• Technical networks: heating, air conditioning, irrigation,
water dispensers.
• Fire suppression systems: sprinklers, fire hoses.
• Professional networks: industrial facilities,
surface treatment, chemical industry, agrifood.
• Temporary networks: water supply for trade fair stands,
festivals, exhibitions.
Note: The applications also depend on legislation in the
country of use. Please contact your national authorities
for further information.

Technical specifications

Type of fluid: clears water
Operation: horizontal position
DN 65 to 250 mm, Connections : drilled flanges
Maximum operating pressure: 10 bar (1 MPa)
Minimum inlet pressure: 1.5 bar (150 KPa)
Maximum operating temperature: 65°C

Standards - Approval

Conforms to the following standards: EN1717, EN12729
ACS
BELGAQUA

1. Operating principle

The backflow preventer with verifiable reduced pressure zone
includes:
• three zones: upstream, intermediate and downstream, each
equipped with a pressure measuring device.
• two independent check valves, separating the intermediate
zone.
• one automatic relief device connected to the intermediate
zone to restore it to atmospheric pressure in the event of a
failure.
This device is installed with a funnel with air gap.
Maintenance and accessibility of the internal components are
facilitated by the modular design of the replacement parts.
INTERMEDIATE CHAMBER
UPSTREAM
1st
VALVE
RELIEF VALVE
Kiwa UK-REG 4
DOWNSTREAM
2nd
VALVE
FUNNEL
3

Publicité

loading