3 - INSTALLATION
F
3.1 - CHOOSING THE LOCATION
GB
• This unit is designed to be installed in sheltered rooms (IP 20).
• Do not install the device in a room containing infl ammable, alkaline, acidic, greasy or very damp air, nor in one where water
I
is liable to be projected. The components will be irremediably damaged.
• Choose the most central position in the room.
• Check that the ceiling is suffi ciently sturdy to support the unit's weight.
E
• In the position chosen, check that no obstacle will impede installation and maintenance (beam, insuffi cient false ceiling height,
fi xed false ceiling panels, access impossible for maintenance, etc.).
D
• Provide an access for easy maintenance, namely for the electrical box and valve(s).
• Provide for the water pipes, electric cables and the condensate discharge outlet.
• Air must be able to circulate freely around the unit.
Electrical box
3.2 - INSTALLATION
• Use the drilling template provided (2) to determine the
position of the suspension rods (1).
• The template must be placed between 2 "T" rails of the false
ceiling.
• Install the suspension rods (not supplied).
• Place the side where the connections are located in the most
appropriate position.
• The "T" rail (3), located on the electrical box side, must be
temporarily removed.
• Put the unit in place and check that it is level.
• Adjust the distance between the unit and the false ceiling (5)
(max. 23 mm) by using the suspension rod nuts.
• Also check the distance between the suspension fl ange (6) and the ceiling (7) (min. 41 mm). A lesser distance may create
noise if the unit touches the ceiling.
3
4
4
Valves
Auxiliary
condensate tank
2
544 x 506
1 m
1 m
1 m
1 m
10
1
7
1 m
544
10
6
5