6. Specifications

MODEL
CAPACITY*
INPUT
Low Line Loss
Voltage Range
Low Line Comeback
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Transfer Time
Inverter
EFFICIENCY
AC mode
Battery Mode
BATTERY
Battery Type
Numbers
Recharge Time
Charging Current
Charging Voltage
PHYSICAL
Dimension,DXWXH(mm)
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Communication port
Software
Optional SNMP
SALES INFORMATION
Warranty
PN
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
51
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 10 19 AA 59 204 31
E4 Value + 6000
6000 VA / 5400 W
100%~110%: 30min; 110%~130%: 5min; >130% : 10sec
100%~110%: 3min; 110%~130%: 30sec; >130% : 10sec
Battery
Bypass
369 x 190 x 688
(battery life cycle will be shorten when temperature is above 25°C)
Less than 55dB @ 1 Meter
Infopower (Supports Windows® 2000/2003/XP/Vista/2008, Windows
Power management from SNMP manager (compatible Vmware
110 VAC ± 3 % at 50% Load;
176 VAC ± 3 % at 100% Load
Low Line Loss Voltage + 10V
300 VAC ± 3 %
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Single phase with ground
≧ 0.99 at 100% Load
208/220/230/240VAC
± 1%
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
3:1 max
≦ 3 % THD (Linear Load)
≦ 5 % THD (Non-linear Load)
0 ms
0 ms
> 92%
> 90%
12 V / 9 Ah
16
9 hours recover to 90% capacity
Default : 1 A ± 10%
Max.: 1A, 2A (Adjustable)
218.4V ± 1%
60
0 ~ 40°C
<95 % and non-condensing
<1000m
RS-232 / USB
Unix, and MAC)
2 years
67656
E4 Value + 10K
10000 VA / 9000 W
> 93%
> 91%
20
442 x 190 x 688
75
Less than 58dB @ 1 Meter
®
7/8, Linux,
©
) and web browser
67657