Interface
06: reserved
⚫
Interface
07: reserved
⚫
Interface
08: Bypass mode setting
⚫
Interface
09: Battery maximum discharge time setting
⚫
Interface
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
43
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 10 19 AA 59 204 31
Setting
reserved
Setting
reserved
Setting
reserved
Setting
Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass
mode depending on bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it's not allowed for
running in Bypass mode under any situations.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass
means users manually operate UPS for Bypass mode. For
example, pressing OFF button in AC mode to turn into Bypass
mode.
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0 min. to 999
min. UPS will shut down to protect battery after discharge time
arrives. The default value is 990 min.
DIS: Disable battery discharge protection and backup time will
depend on battery capacity.