Mounting support legs for VERTICAL AIR DISCHARGE
Ø 500 - 630 - 710 mm models (BRE & i-BRE)
If the unit is installed in places particularly subject to critical conditions such as:
- snowfall,
- sand storms,
- dense vegetation with danger of falling leaves,
- other critical conditions
the condenser must be covered over, leaving the re-
commended working spaces (see paragraph: WOR-
KING SPACE) to maintain a correct airflow, correct
unit heat exchange and correct operation of the unit
in general.
EARTH
Earthing/grounding is compulsory by law. The instal-
ler must connect the earth wire, already connected
to earth/ground electrodes, to a point on the applian-
ce (earth/ground metric screw)
For BRC/BRE: in the low temperature, "LT" , versions, a check valve must be installed on the condenser outlet.
Such valve has to be installed between 1 & 3 meters from indoor unit and its flow has to be placed versus indoor unit.
Place the external condenser BRC/BRE/i-BRE with gas inlet from the top and the liquid output from the bottom. (See above
picture)