Secury 2116 S / 2119 S; Function Control Of The Monitoring Contacts - G-U SECURY 21 EK Notice De Montage

Masquer les pouces Voir aussi pour SECURY 21 EK:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.1.3 SECURY 2116 S / 2119 S

Check whether all latchbolts are completely pulled back when the inside
lever handle is actuated (panic function).
Check whether the inside lever handle can be pushed down easily.
Release the lever handle so that it returns to its initial position.
Check whether the three latchbolts are run out automatically and com-
pletely through pressing on the trigger lever.
Only for SECURY 2116 S (Multi-point lock for 1-leaf doors):
Make sure that all three latchbolts are completely extended.
Check through pressing on the latchbolts (max. 20 N) whether they are
secured against being forced back.
Check whether all latchbolts are completely pulled back when the lock-
ing cylinder / cylinder cam is actuated.
Make sure that, after the test, all latchbolts are pulled back, i.e. all latch-
bolts are in the initial position.
4.2

Function control of the monitoring contacts

Check with the tester (Art. no. B 5599 0023) whether the monitoring con-
tacts of the multi-point locks work properly (For terminal assignment of the
monitoring functions, see chapter 3.3).
SECURY 2170 / 2171 / 2178:
Cylinder cam / position of the key (initial position or actuated)
Outside lever handle (actuated or not actuated)
Inside lever handle (actuated or not actuated)
SECURY 2116 S / 2119 S:
Latchbolt (locked or not locked)
Cylinder cam / position of the key (initial position or actuated)
55

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Secury 21 s

Table des Matières