7 Installation – Electrical (cont.)
SWITCHES
LOCK STATUS RELAY CONTACTS (SPDT)
- Relay dry contacts are rated 1A at 24 VDC for safe operation,
DO NOT exceed this rating.
- If a NO switch is required, connect the wires from the system to
Terminal 3 and Terminal 4.
- If a NC switch is required, connect the wires from the system to
Terminal 4 and Terminal 5.
DOOR STATUS SWITCH
- Connect the positive (+) lead from the power source to the
black wire of the Door Status Sensor switch.
- Connect the negative (-) lead from the power source to one
end of the light for door status.
- Connect the red or green wire of the Door Status Sensor switch
to the other end of the light for door status.
red = light off with door closed
green = light on with door closed
- Reed switch dry contacts are rated 0.25 amp at 30 VAC/VDC
for safe operation. Do not exceed this rating.
BEA INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
BEA Inc., the sensor manufacturer, cannot be held responsible for incorrect installations or inappropriate adjustments or the sensor/device; therefore, BEA Inc. does not
guarantee any use of the sensor outside its intended purpose.
BEA Inc. strongly recommends that installation and service technicians be AAADM-certifi ed for pedestrian doors, IDA-certifi ed for doors/gates, and factory-trained for
the type of door/gate system.
Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor system installation
and/or device is compliant with local, national, and international regulations, codes, and standards.
Once installation or service work is complete, a safety inspection of the system should be performed and documented per the manufacturers recommendations, or
industry guidelines. Examples of compliance may apply to ANSI 156.10, ANSI 156.19, ANSI/DASMA 102, ANSI/DASMA 107, UL325, UL294, International Building Code.
Tech Support: 1-800-407-4545 | Customer Service: 1-800-523-2462 | General Tech Questions: Tech_Services@beainc.com | Tech Docs: www.BEAinc.com
Page 4 of 4
Page 4 of 4
Page 4 of 4
POWER
LOCK STATUS RELAY (SPDT)
SUPPLY
+
-
1
2
3
4
5
+
-
NO
C
NC
SELECTOR
(600 lb)
+ -
0 - 90 SEC.
RELOCK TIMER
DOOR STATUS SENSOR SWITCH*
DOOR STATUS SENSOR SWITCH*
+
BLACK
BLACK
-
sw
ON
ON
* Switch changes state when door is open
* Switch changes state when door is open
1
2
3
4
5
+
-
NO
C
NC
POWER
POWER
SUPPLY
JUMPER
12VDC
(1200 lb)
24VDC
RED
RED
NC
NC
COM
COM
NO
NO
GREEN
GREEN
REED SWITCH
REED SWITCH
MAGNETIC LOCK
MAGNETIC LOCK
1
1
PCB
PCB
2
2
75.5366.07 UL MAGLOCKS 20171130
75.5366.07 UL MAGLOCKS 20171130
75.5366.07 UL MAGLOCKS 20171130
R B G
R
G
B
W
LOCK STATUS RELAY (SPDT
LIGHT
LIGHT